2013-09-16 16:49:59 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) SPECIFY THE SIZE AND TYPE OF ALL WINDOWS THAT ARE |
| BEING REPLACED ON THE PLANS. (IE SINGLE HUNG, |
| HORIZONTAL SLIDING) CITY AMENDMENTS 107.2.1 AND FBCR |
| 301.2.1 |
| |
| 2) SPECIFY THE SIZE OF THE ARCHED FIXED GLASS WINDOW |
| ABOVE THE 52" X 50" WINDOW IN THE MASTER BEDROOM. FBCR |
| 301.2.1 |
| |
| 3) SHOW THAT THE NEW BEDROOM WINDOWS WILL COMPLY WITH |
| FBCR 310 FOR EMERGENCY ESCAPE AND RESCUE OPENINGS. |
| |
| 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE FOR THE |
| STRUCTURAL MULLIONS SHOWN AT THE BEDROOM ADJACENT TO |
| THE GARAGE AND FOR THE CONNECTION OF THE ARCHED F.G. TO |
| THE MASTER BEDROOM WINDOW. DCA RULE 9N-3 |
| |
| 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE DOUBLE |
| OUTSWING FRENCH DOORS WITH SIDELITES SPECIFIED ON THE |
| PLANS AT THE FLORIDA ROOM. SPECIFY THE SIZE OF THE |
| SIDELITES ON THE PLANS. DCA RULE 9N-3 AND FBCR 301.2.1 |
| |
| 6) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. ALSO |
| INDICATE THE SPECIFIC WINDOW OR DOOR SIZE, TYPE OF |
| GLASS, AND DESIGN PRESSURE LISTED IN THE NOA THAT IS TO |
| BE INSTALLED. CITY AMENDMENTS 107.3.4.1 AND FBCR |
| 301.2.1 |
| |
| 7) THE 8' X 7' FIXED GLASS WINDOWS AT THE FLORIDA ROOM |
| ARE LARGER THAN THE MAXIMUM SIZE OF 4' X 8' ALLOWED BY |
| NOA NO. 13-0502.03 FOR THE PGT F.G. WINDOWS. PLEASE |
| INDICATE HOW THIS WILL BE RESOLVED. DCA RULE 9N-3 AND |
| FBCR 301.2.1 |
| |
| 8) THE WIND PRESSURES WERE NOT SPECIFIED FOR THE 52" X |
| 50" WINDOWS W/ ARCH AT THE MASTER BEDROOM AND KITCHEN. |
| PLEASE CLARIFY. |
| |
| 9) IN ORDER TO LESSEN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS HAVE |
| BEEN ADDRESSED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |