2013-11-05 17:03:58ARE PANELBOARD BUS STABS RATED FOR 150A BRANCH BREAKER?
 PLAN SHOWS STAIRS TO LEVEL 2 BUT NO DETAILS - ON
 ORIGINAL SUBMISSION
 DEPENDING ON CONFIGURATION AND LAYOUT, ADDITONAL EM
 LIGHTS MAY BE REQUIRED FOR SAFETY AROUND MACHINERY AND
 FOR EXITING
 WHERE IS PANEL A-2-C AND WHAT ARE THE LOADS? - ON
 ORIGINAL SUBMISSION
 ELECTRICAL LOAD CALCULATION REQUIRED SHOWING MOTOR
 LOADS, MACHINERY LABELS AND LOADS, CONTINUOUS LOADS AT
 125%
 PROVIDE ENERGY CODE CALCULATION FOR ENERGY BUDGET AND
 CONSUMPTION
 SMOKE DETECTORS ARE SHOWN ON PLANS AND NO FACP IS
 INDICATED, PLEASE EXPLAIN THE DESIGN OF THE SYSTEM
 #6 CONDUCTORS NOT RATED 80 AMPS (MILL #1)
 WATER FOUNTAIN RECEPTACLE TO BE INDICATED AS GFCI OR
 GFCI PROTECTED