Plan Review Notes For Permit 13090220 |
Permit Number |
13090220 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-11-05 17:03:58 | ARE PANELBOARD BUS STABS RATED FOR 150A BRANCH BREAKER? | | PLAN SHOWS STAIRS TO LEVEL 2 BUT NO DETAILS - ON | | ORIGINAL SUBMISSION | | DEPENDING ON CONFIGURATION AND LAYOUT, ADDITONAL EM | | LIGHTS MAY BE REQUIRED FOR SAFETY AROUND MACHINERY AND | | FOR EXITING | | WHERE IS PANEL A-2-C AND WHAT ARE THE LOADS? - ON | | ORIGINAL SUBMISSION | | ELECTRICAL LOAD CALCULATION REQUIRED SHOWING MOTOR | | LOADS, MACHINERY LABELS AND LOADS, CONTINUOUS LOADS AT | | 125% | | PROVIDE ENERGY CODE CALCULATION FOR ENERGY BUDGET AND | | CONSUMPTION | | SMOKE DETECTORS ARE SHOWN ON PLANS AND NO FACP IS | | INDICATED, PLEASE EXPLAIN THE DESIGN OF THE SYSTEM | | #6 CONDUCTORS NOT RATED 80 AMPS (MILL #1) | | WATER FOUNTAIN RECEPTACLE TO BE INDICATED AS GFCI OR | | GFCI PROTECTED |
|