2013-09-17 15:52:09PERMIT #13090126
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE CLEAR WIDTH OF ANY CORRIDOR OR PASSAGEWAY SERVING
 AN OCCUPANT LOAD OF 50 OR MORE SHALL BE NOT LESS THAN
 44 INCHES.
  
 PER SECTION 7.5.2.1, ACCESS TO AN EXIT SHALL NOT BE
 THROUGH KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN
 CHAPTERS 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS,
 BEDROOMS OR SIMILAR SPACES, OR OTHER ROOMS OR SPACES
 SUBJECT TO LOCKING.
  
  