Plan Review Notes For Permit 13090073 |
Permit Number |
13090073 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-09-14 08:27:29 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. SEE FBC 2010 EXISTING BUILDING 611.8 REGARDING | | MITIGATION MEASURES FOR THIS STRUCTURE. | | | | 2ND REVIEW, RESPONSE WAS THAT THIS HOUSE WAS BUILT IN | | 1988. THIS LIKELY MEANS THAT THE HOUSE WAS CO'D IN 1988 | | AND NO INFORMATION IS AVAILABLE REGARDING THE EXISTING | | ROOF TO WALL CONNECTORS. SOMEONE OTHER THAN THE | | QUALIFIER HAS WRITTEN A NOTE THAT "WE WILL MAKE SURE | | STRAP HAS THREE NAILS TO CODE." | | | | THE COUNTY'S FORM IS ACCEPTABLE AS A METHOD OF SHOWING | | COMPLIANCE BUT THE FORM MUST BE COMPLETED IN ENTIRETY. | | HOUSE DOES NOT MEET EXCEPTION INDICATED IN ITEM 1 ON | | THE FORM PROVIDED (BUILT AFTER 1988) AND THIS IS NOT | | ACCEPTABLE UNLESS WE HAVE ACCESS TO PLANS AND | | INSPECTION RECORDS, WHICH MUST BE PROVIDED BY | | CONTRACTOR. | | | | 2. TWO SETS OF ALL DOCUMENTS REQUIRED, FBC 107. | | |
|