Plan Review Notes For Permit 13090037 |
Permit Number |
13090037 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-09-16 15:34:09 | FIRST REVIEW | | | | PLANS APPROVED WITH EXCEPTION. MECHANICAL SCHEDULE | | SHOWS MOCP FOR CU TO BE 30 AMPS. ELECTRICAL PANEL | | SCHEDULE SHOWS A 40 AMP BREAKER. PLEASE CLARIFY | | | | PLEASE PROVIDE A 2ND GROUND ROD TO MEET REQUIRED OHM | | RESISTANCE | | | | VB |
|