Plan Review Notes For Permit 13090036 |
Permit Number |
13090036 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-09-16 15:51:15 | FIRST REVIEW - 9-16-13 | | | | APPROVED WITH EXCEPTION | | | | 1. PLEASE PROVIDE 2 GROUND RODS AS INDICATED | | 2. MAX OCP FOR AHU ON MECH SCHEDULE IS 30. PANEL | | SCHEDULE ON E-1 SHOWS 45 AMPS. PLEASE CLARIFY. | | 3. MAX OCP FOR CU ON MECH SCHEDULE SHAOW 35A. PANEL | | SCHEDULE ON E-1 SHOWS 40 AMPS. PLEASE CLARIFY | | VB |
|