Plan Review Notes
Plan Review Notes For Permit 13090036
Permit Number 13090036
Review Stop E
Sequence Number 1
Notes
Date Text
2013-09-16 15:51:15FIRST REVIEW - 9-16-13
  
 APPROVED WITH EXCEPTION
  
 1. PLEASE PROVIDE 2 GROUND RODS AS INDICATED
 2. MAX OCP FOR AHU ON MECH SCHEDULE IS 30. PANEL
 SCHEDULE ON E-1 SHOWS 45 AMPS. PLEASE CLARIFY.
 3. MAX OCP FOR CU ON MECH SCHEDULE SHAOW 35A. PANEL
 SCHEDULE ON E-1 SHOWS 40 AMPS. PLEASE CLARIFY
 VB