2013-09-04 08:00:402010 FBC
  
 DENIED BY BUILDING
  
 1) THE CERTAINTEED SYSTEM ON PAGE 28 SPECIFIED FOR THE
 FLAT ROOF HAS A MAXIMUM DESIGN PRESSURE OF -52.5 PSF.
 THE STRUCTURE IS LOCATED IN AREA WITH 170 MPH VULT/132
 MPH VASD WIND SPEED AND THE EXPOSURE CATEGORY IS C.
 THEREFORE, THE UPLIFT PRESSURES FOR ROOF ZONES 2 AND 3
 ARE MORE THAN THE DESIGN PRESSURE OF THE ROOF SYSTEM.
 SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING IN THE PERIMETER
 (ROOF ZONE 2) AND CORNER (ROOF ZONE 3) AREAS OF THE
 FLAT ROOF. SEE LIMITATION #7 ON PAGE 32 OF THE NOA
 WHICH ALLOWS ENHANCED FASTENING TO INCREASE THE UPLIFT
 PRESSURES IN THESE AREAS. FBC R301.2.1
  