2013-09-11 12:34:26 | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | SHEET A-1 PLUMBING RISER SHOWS THE PUMP DISCHARGE TO A | | VENT. | | 712.3.5 EJECTOR CONNECTION TO THE DRAINAGE SYSTEM. | | PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO | | THE BUILDING SEWER OR SHALL CONNECT TO A WYE FITTING IN | | THE BUILDING DRAIN A MINIMUM OF 10 FEET (3048 MM) FROM | | THE BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE | | DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO | | HORIZONTAL DRAINAGE PIPING, THE CONNECTOR SHALL BE MADE | | THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE | | PIPING. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|