Plan Review Notes
Plan Review Notes For Permit 13081204
Permit Number 13081204
Review Stop M
Sequence Number 1
Notes
Date Text
2013-09-11 10:04:212010 FBC
  
 DENIED BY MECHANICAL
  
 A NEW AIR HANDLER AND CONDENSER UNIT ARE SHOWN ON THE
 PLANS.
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS IN
 ACCORDANCE WITH ACCA MANUAL J FOR THE HVAC EQUIPMENT.
 FBCR M1401.3
  
 2) SUBMIT TWO SETS OF MECHANICAL PLANS. FBCR M1601.1
 SHOW THE DUCT LOCATION AND SIZE. SPECIFY THE SUPPLY
 GRILL SIZES AND CFMS AT EACH DROP. SPECIFY THE RETURN
 LOCATIONS, DUCT AND GRILL SIZES AND SHOW COMPLIANCE
 WITH FBC M1602.4 FOR BALANCED RETURN AIR.
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL
 PLANS.
  
 4) PROVIDE AN ANCHORING DETAIL CAPABLE OF RESISTING THE
 APPLICABLE WIND PRESSURES FOR THE EXTERIOR EQUIPMENT.
 FBCR M1307.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]