Plan Review Notes
Plan Review Notes For Permit 13081204
Permit Number 13081204
Review Stop B
Sequence Number 1
Notes
Date Text
2013-09-11 11:47:122010 FBC
  
 1) THE PERMIT APPLICATION INDICATES THE ADDITION IS TO
 BE STORAGE AND THE PLANS DO NOT SPECIFY THE ROOM USE.
 BASED ON THE PLANS THAT WERE SUBMITTED THE ADDITION
 APPEARS TO BE A BEDROOM OR COULD BE USED AS A BEDROOM
 BY AN OWNER IN THE FUTURE. PLEASE CLARIFY BY LABELING
 THE ROOM ON THE PLANS.
  
 2) THE PLANS SPECIFY THAT THE SPACE WILL BE
 CONDITIONED. SUBMIT TWO COPIES OF ENERGY CALCULATIONS
 FOR THE BUILDING. FBC ENERGY CONSERVATION SECTIONS
 101.4.3 , 101.4.5
  
 3) SHOW COMPLIANCE WITH FBCR 318 FOR TERMITE
 PROTECTION.
  
 4) FBC R403.1.4 REQUIRES ALL EXTERIOR FOOTINGS TO BE
 PLACED AT LEAST 12 INCHES BELOW GRADE AND FBC R317.1
 (5) REQUIRES PROTECTION OF WOOD AND WOOD PRODUCTS FROM
 DECAY FOR WALL FRAMING AND SHEATHING AT THE EXTERIOR OF
 A BUILDING HAVING A CLEARANCE OF LESS THAN 6" FROM THE
 GROUND. THE 16" DEEP FOOTING SPECIFIED ON THE PLANS
 WILL ONLY PROVIDE 4" FROM THE GROUND. SPECIFY HOW THIS
 REQUIREMENT WILL BE ADDRESSED.
  
 5) SHOW COMPLIANCE WITH FBCR 318.6 WHICH REQUIRES
 GUTTERS AND DOWNSPOUTS AT THE REAR OF THE STRUCTURE
 WITH NO EAVE PROJECTION WHERE THE RAIN WATER FROM THE
 ROOF IS DISCHARGED.
  
 6) SHOW COMPLIANCE WITH FBCR 806 FOR REQUIRED ATTIC
 VENTILATION.
  
 7) PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE 4 X 10
 WOOD BEAM AT THE COVERED PORCH IS TO BE NOTCHED INTO
 THE CORNERS AT EACH END (INCLUDING THE EXISTING
 CORNER). SPECIFY THE NUMBER OF FRAMING MEMBERS REQUIRED
 FOR BEARING AND THE REQUIRED STRAPS AND CONNECTORS FOR
 UPLIFT AND LATERAL FORCES. FBC R301.1
  
 8) PLEASE CLARIFY IF THE (3) #5 BARS IN THE FOOTING ARE
 TO BE DOWELED INTO THE EXISTING FOOTING. FBC R301.1
  
 9) PROVIDE A STRUCTURAL DETAIL OF THE PARAPET
 CONSTRUCTION. SHOW ALL CONNECTORS REQUIRED TO ACHIEVE A
 CONTINUOUS LOAD PATH. FBC R301.1
  
 10) PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE
 REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD FOR THE PROJECT. CITY AMENDMENTS 10
  
 11) SUBMIT (2) COPIES OF PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOOR, THE ROOF TILE AND THE SIMPSON CONNECTORS
 AS REQUIRED BY DCA RULE 9N-3.
  
 12) SPECIFY WHICH METHOD OF ATTACHMENT LISTED IN THE
 ROOF TILE PRODUCT APPROVAL WILL BE USED TO INSTALL IT.
 IF AN ADHESIVE IS USED, SUBMIT TWO COPIES OF THE
 PRODUCT APPROVAL. FBC R905.1
  
 13) SPECIFY THE APPROVED ASSEMBLY, INSULATION TYPE,
 FASTENING OPTION AND MAXIMUM DESIGN PRESSURE FROM THE
 MULE- HIDE ROOFING PRODUCT APPROVAL (NOA # 12-0815.09)
 THAT WILL BE USED. IF ENHANCED FASTENING OF THE BASE
 SHEET IS REQUIRED TO MEET THE UPLIFT PRESSURE
 REQUIREMENTS OF THE PERIMETER AND CORNER ROOF AREAS
 SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS IN ACCORDANCE WITH LIMITATION #7 ON PAGE
 25 OF THE NOA. FBC R905.1
  
 14) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THE
 REVIEW COMMENTS HAVE BEEN ADDRESSED. THIS WILL AID IN
 SPEEDING REVIEW TIMES.
  