Plan Review Notes
Plan Review Notes For Permit 13081179
Permit Number 13081179
Review Stop B
Sequence Number 3
Notes
Date Text
2013-09-11 08:15:12THIRD COURTESY REVIEW VIA EMAIL:
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 AS IT APPEARS FROM MANUFACTURER'S EMAIL THAT THIS
 PRODUCT HAS NOT ACTUALLY BEEN TESTED TO THE STANDARD
 LISTED IN THEIR LITERATURE, EITHER HAVE THE PRODUCT
 TESTED (ASTM E-84, SEE PREVIOUS COMMENT LISTS) OR
 SUBMIT ENGINEERING AND/OR TEST REPORTS FBC 104.11
 ALTERNATIVE MATERIALS AND METHODS:
  
 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT. THE PROVISIONS OF THIS CODE
 ARE NOT INTENDED TO PREVENT THE INSTALLATION OF ANY
 MATERIAL OR TO PROHIBIT ANY DESIGN OR METHOD OF
 CONSTRUCTION NOT SPECIFICALLY PRESCRIBED BY THIS CODE,
 PROVIDED THAT ANY SUCH ALTERNAT IVE HAS BEEN APPROVED.
 AN ALTERNATIVE MATERIAL, DESIGN OR METHOD OF
 CONSTRUCTION SHALL BE APPROVED WHERE THE BUILDING
 OFFICIAL FINDS THAT THE PROPOSED DESIGN IS SATISFACTORY
 AND COMPLIES WITH THE INTENT OF THE PROVISIONS OF THIS
 CODE, AND THAT THE MATERIAL, METHOD OR WORK OFFERED IS,
 FOR THE PURPOSE INTENDED, AT LEAST THE EQUIVALENT OF
 THAT PRESCRIBED IN THIS CODE IN QUALITY, STRENGTH,
 EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY.
 WHEN ALTERNATE LIFE SAFETY SYSTEMS ARE DESIGNED, THE
 SFPE ENGINEERING GUIDE TO PERFORMANCE-BASED FIRE
 PROTECTION ANALYSIS AND DESIGN OF BUILDINGS, OR OTHER
 METHODS APPROVED BY THE BUILDING OFFICIAL MAY BE USED.
  
 THE BUILDING OFFICIAL SHALL REQUIRE THAT SUFFICIENT
 EVIDENCE OR PROOF BE SUBMITTED TO SUBSTANTIATE ANY
 CLAIM MADE REGARDING THE ALTERNATIVE.
  
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR
 ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE,
 SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED
 SOURCES.
  
 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT EVIDENCE
 OF COMPLIANCE WITH THE PROVISIONS OF THIS CODE, OR
 EVIDENCE THAT A MATERIAL OR METHOD DOES NOT CONFORM TO
 THE REQUIREMENTS OF THIS CODE, OR IN ORDER TO
 SUBSTANTIATE CLAIMS FOR ALTERNATIVE MATERIALS OR
 METHODS, THE BUILDING OFFICIAL SHALL HAVE THE AUTHORITY
 TO REQUIRE TESTS AS EVIDENCE OF COMPLIANCE TO BE MADE
 AT NO EXPENSE TO THE JURISDICTION. TEST METHODS SHALL
 BE AS SPECIFIED IN THIS CODE OR BY OTHER RECOGNIZED
 TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED AND
 ACCEPTED TEST METHODS, THE BUILDING OFFICIAL SHALL
 APPROVE THE TESTING PROCEDURES. TESTS SHALL BE
 PERFORMED BY AN APPROVED AGENCY. REPORTS OF SUCH TESTS
 SHALL BE RETAINED BY THE BUILDING OFFICIAL FOR THE
 PERIOD REQUIRED FOR RETENTION OF PUBLIC RECORDS.
  
 SEE ALSO:
  
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  