| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS ARE |
| REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. PLANS |
| DO NOT INDICATE THE LOCATE AND QUANTITIES OF THESE |
| DEVICES. |
| |
| A SEPARATE ELECTRICAL PERMIT MAY BE NEEDED TO POWER THE |
| EXIT SIGNS/EMERGENCY LIGHTS. |
| |
| PROVIDE A TABLE AND SEATING LAYOUT. |
| |
| PLANS INDICATE A FIRE PIT. GENERALLY FIRE AND OPEN |
| FLAME IS NOT PERMITTED AT THESE TYPES OF EVENTS. PLEASE |
| PROVIDE ADDITIONAL INFORMATION SUCH AS PIT SIZE, FUEL, |
| SAFEGUARDS, ETC. |
| |
| PLANS DO NOT INDICATE THE LOCATIONS OF FIRE |
| EXTINGUISHERS. PROVIDE PORTABLE FIRE EXTINGUISHERS. |
| EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC |
| AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER |
| COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT |
| EXCEED 75 FEET. PROVIDE TYPE K EXTINGUISHERS WHEN |
| COOKING WITH GREASE OR WHEN PRODUCING SMOKE OR |
| GREASE-LADEN VAPORS. |
| |
| TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| BUILDING STRUCTURES. |
| |
| POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| LOCATIONS. |
| |
| GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES |
| SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET |
| AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| ENCLOSURE. |
| |