2013-09-11 07:52:32 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| AREA WITH AN A5 FLOOD ZONE DESIGNATION. THE MINIMUM |
| BASE FLOOD ELEVATION IS 7' 6", WHICH INCLUDES A 6" |
| FREEBOARD ESTABLISHED BY CITY OF WEST PALM BEACH |
| ORDINANCE. THE VALUE OF THE PROPOSED WORK WHEN ADDED TO |
| PREVIOUS WORK DONE TO THE STRUCTURE IS OVER 50 PERCENT |
| OF THE VALUE OF THE STRUCTURE BASED ON THE PALM BEACH |
| COUNTY PROPERTY APPRAISER. THEREFORE, THIS IS |
| CONSIDERED A SUBSTANTIAL IMPROVEMENT AND THE ENTIRE |
| STRUCTURE IS REQUIRED TO COMPLY WITH THE REQUIRED |
| ELEVATION PER FEMA AND CITY ORDINANCE. SUBMIT AN |
| ELEVATION CERTIFICATE THAT SHOWS THE EXISTING STRUCTURE |
| AND EQUIPMENT ARE IN COMPLIANCE OR INDICATE HOW IT WILL |
| BE BROUGHT INTO COMPLIANCE. |
| |
| 2) ON SHEET A100, THE 2007 FBC W/2010 AMENDMENTS IS |
| SPECIFIED. THIS IS INCORRECT. THE APPLICABLE CODE IS |
| THE 2010 FBC EXISTING BUILDING. THIS IS A LEVEL 2 |
| ALTERATION. PLEASE CORRECT THE DESIGN DATA BOX AND |
| GENERAL NOTES #1 AND #10. |
| |
| 3) ALSO ON SHEET A100 THE DESIGN DATA BOX INCORRECTLY |
| SPECIFIES TYPE 1-A CONSTRUCTION. THIS STRUCTURE IS A |
| SINGLE FAMILY DWELLING AND IS TYPE V-B CONSTRUCTION. |
| PLEASE CORRECT. |
| |
| 4) GENERAL NOTE #1 SPECIFIES COMPLIANCE WITH AMENDMENTS |
| ADOPTED BY THE TOWN OF PALM BEACH. THIS PROJECT IS |
| LOCATED IN THE CITY OF WEST PALM BEACH, THEREFORE, ONLY |
| THE CITY OF WEST PALM BEACH AMENDMENTS WOULD APPLY. |
| PLEASE CORRECT. |
| |
| |