 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL OF THE NOTIFICATION APPLIANCES ARE SHOWN AS EITHER
 15 OR 30 CANDELA WHICH RESULTS IN INADEQUATE STROBE
 INTENSITY THROUGHOUT MUCH OF THE SUITE. THE FIRE ALARM
 ENGINEERING DOCUMENTS FOR THE MASTER PERMIT (#1305015)
 INDICATE THESE APPLIANCES TO BE 75 CANDELA UNLESS
 OTHERWISE NOTED.
  