2013-09-04 13:37:23FIRST REVIEW -9-4-13
 1.PROVIDE PANEL SCHEDULE PER NEC 408.4
 2. ALL NEW OUTLETS TO BE TAMPER RESISTANT AND AFCI
 PROTECTED PER NEC 406.11 AND 210.12B
 3. SHOW CIRCUITRY AND ROOM NAMES FOR CLARITY ON
 ELECTRICAL PLANS
 4. PROVIDE LOAD CALCS WITH ALL ADDITIONAL APPLIANCES,
 FIXTURES AND CIRCUITS PER NEC 220
 5. PROVIDE SMOKE ALARMS PER FLORIDA RESIDENTIAL CODE
 SECTION 314 IF NOT ALREADY EXISTING
 END OF REVIEW - VB
  