2013-08-27 07:59:45 | BUILDING PLAN REVIEW |
| PERMIT: 13080997 |
| ADD: 622 N FLAGLER DR # 204 |
| CONT: HEDRICK BROTHERS |
| TEL: (561)689-8880 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| DATE: TUESDAY AUGUST 27/ 2013 |
| ACTION: BUILDING PROVISO |
| |
| FLOORING: IF JUST REPLACING FLOOR TILE IT IS CONSIDERED |
| A REPAIR, IF THE WHOLE FLOOR IN THE ROOM IS BEING |
| REPLACE THEN IT IS CONSIDERED NEW CONSTRUCTION AND WILL |
| NEED TO COMPLY WITH: |
| 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING |
| FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| |
| 1C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FBC-B 2010 |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| |