Plan Review Notes
Plan Review Notes For Permit 13080942
Permit Number 13080942
Review Stop E
Sequence Number 1
Notes
Date Text
2013-10-16 13:31:37THIS FILE HAS BEEN APPROVED WITH THE HEREIN DESCRIBED
 EXCEPTIONS WHICH SHALL BE BE REQUIRED FOR SUCCESSFUL
 INSPECTIONS.
  
 FROM THE PERMIT APPLICATION, I GATHER THAT THIS
 STRUCTURE WAS BUILT WITHOUT THE BENEFIT OF A PERMIT AND
 OR INSPECTIONS SOME TIME AGO. REGARDLESS OF THE TIME IT
 WAS BUILT, IT IS CURRENTLY BEING PERMITTED; THEREFORE
 IT SHALL COMPLY WITH CURRENT CODE REQUIREMENTS AS
 FOLLOWS:
 1. THE ADDITION OF THIS ROOM MANDATES COMPLIANCE WITH
 THE FBCR 314.
 2. THE ELECTRICAL CIRCUITS WITHING THE AREA IN QUESTION
 (WITHIN THE SCOPE OF THIS PERMIT) SHALL COMPLY WITH NEC
 210.12 (B) AFCI
 3. THE ELECTRICAL DEVICES WITH IN AREA IN QUESTION,
 SHALL COMPLY WITH NEC 406.11 WHICH REQUIRES
 TAMPER-RESISTANT OUTLETS.
 4. THE LIGHT ON THE EXTERIOR OF THE ENTRY DOOR SHALL
 NOT BE BEHIND THE DOOR SWING.
 5. THE SUBMITTED DRAWING DOES NOT INDICATE COMPLIANCE
 WITH NEC 210.52 WITH REGARDS TO PROPER OUTLET PLACING.
 FURTHERMORE, THE DEDICATED OUTLET FOR THE WALL A/C UNIT
 IS SHOWN TO BE 30 AMP AND THUS SHALL NOT BE CONSIDERED
 AS PART OF THE REQUIRED OULTELS ALONG THE WALL LINE,
  
 THOUGH SOME OR ALL OF THE ABOVE MENTIONED REQUIREMENTS
 MAY ALREADY BE IN PLACE, THEY ARE NOT REFLECTED ON THE
 SUBMITTED DRAWING AND THUS MENTIONED HEREIN.
  
 SENT BACK TO BIN FOR FURTHER REVIEWS BY: MA
  
  