2013-10-16 13:31:37 | THIS FILE HAS BEEN APPROVED WITH THE HEREIN DESCRIBED |
| EXCEPTIONS WHICH SHALL BE BE REQUIRED FOR SUCCESSFUL |
| INSPECTIONS. |
| |
| FROM THE PERMIT APPLICATION, I GATHER THAT THIS |
| STRUCTURE WAS BUILT WITHOUT THE BENEFIT OF A PERMIT AND |
| OR INSPECTIONS SOME TIME AGO. REGARDLESS OF THE TIME IT |
| WAS BUILT, IT IS CURRENTLY BEING PERMITTED; THEREFORE |
| IT SHALL COMPLY WITH CURRENT CODE REQUIREMENTS AS |
| FOLLOWS: |
| 1. THE ADDITION OF THIS ROOM MANDATES COMPLIANCE WITH |
| THE FBCR 314. |
| 2. THE ELECTRICAL CIRCUITS WITHING THE AREA IN QUESTION |
| (WITHIN THE SCOPE OF THIS PERMIT) SHALL COMPLY WITH NEC |
| 210.12 (B) AFCI |
| 3. THE ELECTRICAL DEVICES WITH IN AREA IN QUESTION, |
| SHALL COMPLY WITH NEC 406.11 WHICH REQUIRES |
| TAMPER-RESISTANT OUTLETS. |
| 4. THE LIGHT ON THE EXTERIOR OF THE ENTRY DOOR SHALL |
| NOT BE BEHIND THE DOOR SWING. |
| 5. THE SUBMITTED DRAWING DOES NOT INDICATE COMPLIANCE |
| WITH NEC 210.52 WITH REGARDS TO PROPER OUTLET PLACING. |
| FURTHERMORE, THE DEDICATED OUTLET FOR THE WALL A/C UNIT |
| IS SHOWN TO BE 30 AMP AND THUS SHALL NOT BE CONSIDERED |
| AS PART OF THE REQUIRED OULTELS ALONG THE WALL LINE, |
| |
| THOUGH SOME OR ALL OF THE ABOVE MENTIONED REQUIREMENTS |
| MAY ALREADY BE IN PLACE, THEY ARE NOT REFLECTED ON THE |
| SUBMITTED DRAWING AND THUS MENTIONED HEREIN. |
| |
| SENT BACK TO BIN FOR FURTHER REVIEWS BY: MA |
| |
| |