2013-09-04 10:33:07 | FBC 2010 EXISTING BUILDING CODE | | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | THE WATER CLOSETS ARE NOT PROPERLY VENTED AS SHOWN. WET | | VENTING IS ONLY PERMITTED FOR UP TO TWO BATHROOMS AND | | FOUR ARE SHOWN ON THE PLAN. CONNECTING EACH LAVATORY | | STACK TO ITS ASSOCIATED WATER CLOSET BRANCH LINE, | | CREATING FOUR WET VENTED RESTROOMS, WOULD BE OK. | | 909.1 HORIZONTAL WET VENT PERMITTED. | | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS | | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE | | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE | | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND | | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION | | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM | | FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH | | DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT | | INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE | | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL | | WET VENT. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|