2013-08-28 08:39:11 | BUILDING PLAN REVIEW |
| PERMIT: 13080941 |
| ADD: 501 FERN ST UNIT# B1 INTERIOR BUILD-OUT |
| CONT: EDS ISLAND TIME SERVICES |
| TEL: (561)541-0004 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. AUGUST 28/ 2013 |
| ACTION: DENIED |
| |
| 1) ADDITIONAL INFORMATION IS REQUIRED 107.2.1.3, THE |
| STRUCTURAL SHEET S2 DETAIL F & H INCLUDES A VERTICAL |
| STEEL COLUMN WITH A 6"X3"X 1/4" STEEL PLATE WELDED AT |
| ELEVATION 8'-0" ABOVE FINISH FLOOR. IT APPEARS A BOTTOM |
| PLATE STEEL TRACK 14 GAUGE IS ATTACHED TO THE 1/4" |
| STEEL PLATE. THERE IS NO MULLION, OR BUILT UP BOX BEAM, |
| PLEASE PROVIDE HOW THE LOADS ARE GOING TO BE |
| TRANSFERRED WITH NO FRAMING MEMBER, IS THE 14 GAUGE |
| TRACK |
| HEAVY ENOUGH TO TRANSFER THE WIND LOADS. IF YOU COULD |
| PLEASE PROVIDE SOME ADDITIONAL INFORMATION. THANK YOU. |
| |
| 2) THE SUBMITTED PRODUCT APPROVAL (11-1117.02) DOES |
| NEED THE DESIGNER OF RECORD TO REVIEW AND PLACE A SHOP |
| DRAWING STAMP. PRODUCT APPROVALS: 2010 FBC 107.3.4.1 |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| SHEET 3 OF 13 TYPICAL ANCHORS C INDICATES THE FASTENERS |
| TO FASTEN INTO A36 STEEL, PLEASE PROVIDE IF THE 14 |
| GAUGE TRACK MEETS THIS REQUIREMENT. SHEET 9 OF 13 |
| PLEASE CIRCLE THE APPROPRIATE WINDOW SIZE ANCHOR TYPES |
| FOR THE PRESSURES REQUIRED. PLEASE CIRCLE WHICH TYPE OF |
| FASTENERS AND HOW MANY WILL BE REQUIRED FOR EACH SIDE |
| OF THE STRUCTURAL STEEL COLUMN. |
| |
| 3) SHEET A4 INDICATES USE OF A ATTIC SPACE FOR HVAC |
| EQUIPMENT, PLEASE PROVIDE FLOOR LOADING FOR THIS SPACE, |
| 2010 FLBC-B TABLE 1607.1. |
| |
| 4) SHEET A4 & M.2 BOTH INDICATE THE AIR HANDLIER UNITS |
| ARE TO BE ROOF TOP UNITS: |
| 4A) PROVIDE INFORMATION HOW THE COMPRESSORS ARE TO BE |
| MOUNTED TO THE ROOF. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(G) EX |
| PRE-ENGINEERED A/C STANDS |
| |
| 4B) FBC-B TABLE 1509.7 HEIGHT REQUIREMENTS FOR A/C |
| CONDENSOR STANDS LOCATED ON ROOFS. |
| |
| 4C) 2010 FBC-MECHANICAL 306.5 EQUIPMENT AND APPLIANCES |
| ON ROOFS OR ELEVATED STRUCTURES, ACCESS. |
| |
| 4C) IF A ROOF HATCH IS USED, 1009.13.2 PROTECTION AT |
| ROOF HATCH OPENINGS. |
| WHERE THE ROOF HATCH OPENING PROVIDING THE REQUIRED |
| ACCESS IS LOCATED WITHIN 10 FEET (3049 MM) OF THE ROOF |
| EDGE, SUCH ROOF ACCESS OR ROOF EDGE SHALL BE PROTECTED |
| BY GUARDS INSTALLED IN ACCORDANCE WITH THE PROVISIONS |
| OF SECTION 1013. |
| |
| 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |