2013-08-28 08:39:11BUILDING PLAN REVIEW
 PERMIT: 13080941
 ADD: 501 FERN ST UNIT# B1 INTERIOR BUILD-OUT
 CONT: EDS ISLAND TIME SERVICES
 TEL: (561)541-0004
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 28/ 2013
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION IS REQUIRED 107.2.1.3, THE
 STRUCTURAL SHEET S2 DETAIL F & H INCLUDES A VERTICAL
 STEEL COLUMN WITH A 6"X3"X 1/4" STEEL PLATE WELDED AT
 ELEVATION 8'-0" ABOVE FINISH FLOOR. IT APPEARS A BOTTOM
 PLATE STEEL TRACK 14 GAUGE IS ATTACHED TO THE 1/4"
 STEEL PLATE. THERE IS NO MULLION, OR BUILT UP BOX BEAM,
 PLEASE PROVIDE HOW THE LOADS ARE GOING TO BE
 TRANSFERRED WITH NO FRAMING MEMBER, IS THE 14 GAUGE
 TRACK
 HEAVY ENOUGH TO TRANSFER THE WIND LOADS. IF YOU COULD
 PLEASE PROVIDE SOME ADDITIONAL INFORMATION. THANK YOU.
  
 2) THE SUBMITTED PRODUCT APPROVAL (11-1117.02) DOES
 NEED THE DESIGNER OF RECORD TO REVIEW AND PLACE A SHOP
 DRAWING STAMP. PRODUCT APPROVALS: 2010 FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 SHEET 3 OF 13 TYPICAL ANCHORS C INDICATES THE FASTENERS
 TO FASTEN INTO A36 STEEL, PLEASE PROVIDE IF THE 14
 GAUGE TRACK MEETS THIS REQUIREMENT. SHEET 9 OF 13
 PLEASE CIRCLE THE APPROPRIATE WINDOW SIZE ANCHOR TYPES
 FOR THE PRESSURES REQUIRED. PLEASE CIRCLE WHICH TYPE OF
 FASTENERS AND HOW MANY WILL BE REQUIRED FOR EACH SIDE
 OF THE STRUCTURAL STEEL COLUMN.
  
 3) SHEET A4 INDICATES USE OF A ATTIC SPACE FOR HVAC
 EQUIPMENT, PLEASE PROVIDE FLOOR LOADING FOR THIS SPACE,
 2010 FLBC-B TABLE 1607.1.
  
 4) SHEET A4 & M.2 BOTH INDICATE THE AIR HANDLIER UNITS
 ARE TO BE ROOF TOP UNITS:
 4A) PROVIDE INFORMATION HOW THE COMPRESSORS ARE TO BE
 MOUNTED TO THE ROOF.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(G) EX
 PRE-ENGINEERED A/C STANDS
  
 4B) FBC-B TABLE 1509.7 HEIGHT REQUIREMENTS FOR A/C
 CONDENSOR STANDS LOCATED ON ROOFS.
  
 4C) 2010 FBC-MECHANICAL 306.5 EQUIPMENT AND APPLIANCES
 ON ROOFS OR ELEVATED STRUCTURES, ACCESS.
  
 4C) IF A ROOF HATCH IS USED, 1009.13.2 PROTECTION AT
 ROOF HATCH OPENINGS.
 WHERE THE ROOF HATCH OPENING PROVIDING THE REQUIRED
 ACCESS IS LOCATED WITHIN 10 FEET (3049 MM) OF THE ROOF
 EDGE, SUCH ROOF ACCESS OR ROOF EDGE SHALL BE PROTECTED
 BY GUARDS INSTALLED IN ACCORDANCE WITH THE PROVISIONS
 OF SECTION 1013.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  