Plan Review Notes
Plan Review Notes For Permit 13080940
Permit Number 13080940
Review Stop B
Sequence Number 1
Notes
Date Text
2013-08-28 07:29:23BUILDING PLAN REVIEW
 PERMIT: 13080940
 ADD: 501 FERN ST UNIT# B2 INTERIOR BUILD-OUT
 CONT: EDS ISLAND TIME SERVICES
 TEL: (561)541-0004
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 28/ 2013
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS, PLEASE REVIEW A1 THE
 COVERSHEET, A.3 & LS1, THEY LIST THE SAME AREA AS A A2,
 A3 OCCUPANCY AND STUDIO FOR THE SAME AREA, CITY OF WEST
 PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA BUILDING
 CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. PLEASE PROVIDE IN DETAIL WHAT THIS AREA WILL
 BE USED FOR:
 A2 INTENDED FOR FOOD OR DRINK CONSUMPTION
 A3 INTENDED FOR WORSHIP, RECREATION OR AMUSEMENT
  
 2) LS1 INDICATES 2 EXIT DOORS PLEASE PROVIDE COMPLIANCE
 WITH 2010 FBC-B 1015.2.1 TWO EXITS OR EXIT ACCESS
 DOORWAYS. EXCEP #2, WHERE TWO EXITS OR EXIT ACCESS
 DOORWAYS ARE REQUIRED FROM ANY PORTION OF THE EXIT
 ACCESS, THE EXIT DOORS OR EXIT ACCESS DOORWAYS SHALL BE
 PLACED A DISTANCE APART EQUAL TO NOT LESS THAN
 ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED MEASURED
 IN A STRAIGHT LINE BETWEEN EXIT DOORS OR EXIT ACCESS
 DOORWAYS. IT APPEARS THE DISTANCE BETWEEN THE 2 DOORS
 DOES NOT MEET 1/3RD THE DISTANCE OF THE OVERALL
 DIAGONAL BETWEEN THE DOORS.
  
 3) SHEET A3 INDICATES THERE ARE TWO DRESSING ROOMS FOR
 THE MERCANTILE PORTION OF THE TENANT SPACE, PLEASE
 PROVIDE COMPLIANCE WITH:
 2010 FL ACCESSIBILITY CODE DRESSING ROOMS:
 3A) 803.2 TURNING SPACE. TURNING SPACE COMPLYING WITH
 304 SHALL BE PROVIDED WITHIN THE ROOM.
  
 3B) 803.4 BENCHES.
 A BENCH COMPLYING WITH 903 SHALL BE PROVIDED WITHIN THE
 ROOM.
  
 3C)903.3 SIZE.
 BENCHES SHALL HAVE SEATS THAT ARE 42 INCHES (1065 MM)
 LONG MINIMUM AND 20 INCHES (510 MM) DEEP MINIMUM AND 24
 INCHES (610 MM) DEEP MAXIMUM.
  
 3D) 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
  
 ADVISORY 903.4 BACK SUPPORT.
 TO ASSIST IN TRANSFERRING TO THE BENCH, CONSIDER
 PROVIDING GRAB BARS ON A WALL ADJACENT TO THE BENCH,
 BUT NOT ON THE SEAT BACK. IF PROVIDED, GRAB BARS CANNOT
 OBSTRUCT TRANSFER TO THE BENCH.
  
 3E) 903.5 HEIGHT.
 THE TOP OF THE BENCH SEAT SURFACE SHALL BE 17 INCHES
 (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 3F) 803.5 COAT HOOKS AND SHELVES.
 COAT HOOKS PROVIDED WITHIN THE ROOM SHALL BE LOCATED
 WITHIN ONE OF THE REACH RANGES SPECIFIED IN 308.
 SHELVES SHALL BE 40 INCHES (1015 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4) SHEET A3 INDICATES USE OF A ATTIC SPACE FOR HVAC
 EQUIPMENT, PLEASE PROVIDE FLOOR LOADING FOR THIS SPACE,
 2010 FLBC-B TABLE 1607.1.
  
 5) SHEET E1 & M1 BOTH INDICATE THE AIR HANDLIER UNITS
 ARE TO BE ROOF TOP UNITS:
 5A) PROVIDE INFORMATION HOW THE COMPRESSORS ARE TO BE
 MOUNTED TO THE ROOF.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(G) EX
 PRE-ENGINEERED A/C STANDS
  
 5B) FBC-B TABLE 1509.7 HEIGHT REQUIREMENTS FOR A/C
 CONDENSOR STANDS LOCATED ON ROOFS.
  
 5C) 2010 FBC-MECHANICAL 306.5 EQUIPMENT AND APPLIANCES
 ON ROOFS OR ELEVATED STRUCTURES, ACCESS.
  
 5C) IF A ROOF HATCH IS USED, 1009.13.2 PROTECTION AT
 ROOF HATCH OPENINGS.
 WHERE THE ROOF HATCH OPENING PROVIDING THE REQUIRED
 ACCESS IS LOCATED WITHIN 10 FEET (3049 MM) OF THE ROOF
 EDGE, SUCH ROOF ACCESS OR ROOF EDGE SHALL BE PROTECTED
 BY GUARDS INSTALLED IN ACCORDANCE WITH THE PROVISIONS
 OF SECTION 1013.
  
 6) SHEET A.3 INDICATE A CHECK OUT COUNTER FOR THE
 MERCANTILE OCCUPANCY PLEASE SHOW COMPLIANCE WITH: 2010
 FBC-ACCESSIBILITY CODE EITHER 904.32 COUNTERS, 904.3.3
 CHECK WRITING SURFACES AND OR 904.4 SALES AND SERVICE
 COUNTERS.
  
 7) PRODUCT APPROVALS: 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) PERMIT # 13080941 HAS A ATTACHED S3 PLAN WHICH LOOKS
 LIKE IT SHOULD BE ATTACHED TO THIS SET OF PLANS OR MORE
 LIKELY S3 PLANS SHOULD SET IN SETS FOR BOTH PERMITS...
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  