2013-09-17 13:36:03 | FBC 2010 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. SHEETS P-1 & P-2: THE WATER CLOSET IN THE MENS ROOM |
| IS NOT VENTED BY ONE OF THE METHODS IN CHAPTER 9. |
| CONNECTING THE LAVATORY STACK TO THE WATER CLOSET |
| BRANCH WOULD BE OK AS A WET VENT OR IF THE SYSTEM IS A |
| CURCUIT VENT, A VERTICAL DRY VENT WOULD BE REQUIRED |
| BETWEEN THE LAST TWO MOST UPSTREAM FIXTURE BRANCHES. |
| 901.2.1 VENTING REQUIRED. |
| EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN |
| ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN |
| THIS CHAPTER. |
| 911.1 CIRCUIT VENT PERMITTED. |
| 911.2 VENT CONNECTION. |
| THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN |
| THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL |
| CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED |
| IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE |
| SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. |
| |
| 2. SHEETS P-1 & P-2: ALL HOSE BIBBS ARE REQUIRED TO |
| HAVE SEPARATE SHUTOFF VALVES. |
| 606.2 LOCATION OF SHUTOFF VALVES. |
| (2) ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER |
| THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| |
| 3. FLOOR DRAINS WILL BE REQUIRED TO HAVE TRAP PRIMERS. |
| 1002.4 TRAP SEALS. |
| EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS |
| THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 |
| MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO |
| ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO |
| LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE |
| TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A |
| TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR |
| ASSE 1044. |
| |