2013-10-11 16:16:08REVIEWED BY WDS.
  
 1) SHEET E-0 AND E-1 STATES THE PROJECT WAS DESIGNED TO
 THE NEC 2011. REVISE TO COMPLY WITH THE CORRECT EDITION
 OF THE CODE.
 2) SHEET E-1, PANELBOARD "P" SHOWS CIRCUIT P-23 BEING
 USED ON ELECTRICAL FLOOR PLANS. HOWEVER, ON SHEET E-2
 PANELBOARD SCHEDULE CIRCUIT P-23 STATES IT IS A
 "SPARE".
 3) ON PANELBOARD "P" SCHEDULE SHOW CIRCUITS P-28,30,32
 AND P-27,29,31 HAS WATER HEATERS THAT ARE NOT SHOWN ON
 SHEET E-1. HOWEVER, ON SHEET P-1 THE TWO WATER HEATERS
 "A" ARE LOCATED IN THE ELECTORAL ROOM AND THE JANITOR
 CLOSET, PROVIDE THE PROPER CLEARANCE IN FRONT OF THE
 WATER HEATERS. NEC 110.26(A)(1).
 4) PROVIDE DESIGNATION OF ALL RECEPTACLE AND LIGHTING
 CIRCUITS.
 5) DESIGNATE ALL FIXTURES THAT WILL BE ON THE LIGHTING
 CONTROL PANEL AND CIRCUITS.
 6) PROVIDE LISTING APPROVAL FOR LIGHTING CONTROL PANEL
 AND ASSOCIATED DEVISES CONNECT FOR THE SYSTEM.
 7) REVIEW ELECTRICAL CIRCUITS AND FEEDERS TO COMPLY
 WITH FBC ENERGY CONSERVATION CODE SECTION 505.7.3.
 8) PROVIDE LIGHTING STUDY THAT SHOWS THE INTERIOR AND
 EXTERIOR LIGHTING POWER DENSITIES IS IN COMPLIANCE WITH
 FBC ENERGY CONSERVATION CODE SECTION 505.5.3 AND 505.6.
 9) PROVIDE COMPLIANCE WITH FLASH PROTECTION IN
 COMPLIANCE WITH NEC 110.16.
 10) PROVIDE THE AVAILABLE FAULT CURRENT LEVEL AT THE
 LINE TERMINALS OF THE EQUIPMENT. NEC 110.9.
 11) PROVIDE THAT ALL LIGHTING IS LISTED.
 12 PROVIDE PHOTOMETRICS FOR THE INTERIOR AND EXTERIOR
 LIGHTING. FBC 1006.1.
  
 SENT TO C-23.