2013-09-17 11:24:10BUILDING PLAN REVIEW
 PERMIT: 13080851
 ADD: 2815 N FLAGLER DR
 CONT: TYDAN CONSTRUCTION
 TEL: (561)339-5564
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES SEPT 17/ 2013
 ACTION: DENIED
  
 NOTE: PLACES OF WORSHIP ARE EXEMPT FROM THE
 ACCESSIBILITY CODE AND ARE NOT PART OF THIS REVIEW.
  
 1) SHEET S-3:
 1A) SOILS REPORT VERSES THE SECTION B, THE SOILS REPORT
 INDICATES BECAUSE OF THE EXISTING FOOTING DEPTH A
 RETAINING WALL TO BE CONSTRCTED ALONG WITH A INTERFACE
 BETWEEN THE EXISTING BUILDING AND NEW ADDITION. I SPOKE
 WITH THE DESIGNER OF RECORD STEPHAN YECKES ABOUT THIS
 DESCREPANCY IN THE PLANS AAND HE DID INDICATE THE SOILS
 REPORT CAME IN AFTER THE INITIAL DESIGN AND A REVISION
 WILL BE FORTH COMING ON THE NEXT SUBMITION.
  
 1B) THE SECOND QUESTION IS ABOUT WHAT APPEARS TO BE A
 WOODEN RAMP BETWEEN THE EXISTING STRUCTURE AND THE NEW
 ADDITION, ADDITIONAL INFORMATION REQUIRED, IS THERE A
 CONCRETE SLAB BENEATH THIS AREA, OR IS IT GRADE, PLEASE
 ALSO PROVIDE THE LIVE LOADS FOR THIS DESIGN PER 2010
 FBC-B TABLE 1607.1. THE DETAILS OF THE FOUNDATION
 PERMIT 12020320 FOR THIS AREA DO NOT MATCH UP. NEW
 DESIGN?
  
 2) SHEET A1 VS LS1, THE LIFE SAFETY SHEET INDICATES A
 OCCUPANT LOAD OF 297, IN TWO OF THE HEADINGS THE
 ASSEMBLY AND MEZZANINE LEVEL THE PARTIAL OCCUPANT WAS
 ROLLED DOWN, WHEN FIGURING OCCUPANT LOADS WITH A
 PARTIAL OCCUPANT YOU ALWAYS ROUND UP TO THE NEXT WHOLE
 OCCUPANT, BOAF INFORMAL INTERPRETATION # 5479. THIS
 BUMPS THE OCCUPANT LOAD TO 299 OCCUPANTS.
  
 THE OTHER ISSUE WITH THE OCCUPANT LOAD IS THERE IS NO
 OCCUPANT LOAD GIVEN TO THE LOBBY AREA, I HAVE SPOKE
 WITH THE CITY OF WPB B O ROBEERT BROWN ON THIS
 PARTICULAR PLAN. THERE IS A BOAF
 INTERPRETATION 2657 THAT STATES YES AN OCCUPANT LOAD
 MUST BE ASSIGNED TO LOBBY OR ATRIUM AREAS AND AS
 ASSEMBLY WITHOUT FIXED SEATING- CONCENTRATED, BUT IT
 ALSO GOES ON TO SAY THAT THEY SHOULD BE EVALUATED ON A
 CASE- BY CASE BASIS.
  
 MR BROWN HAS REVIEWED THIS PLAN AND BELIEVES THE INTENT
 OR USE OF THIS AREA IS MORE LIKE A CORRIDOR THAN LOBBY,
 IT EXIST BECAUSE OF THE REQUIREMENT OF TWO EXITS
 REQUIRED FROM THE ASSEMBLY OCCUPANCIES LOCATED ON BOTH
 SIDES OF THE CORRIDOR SATISFYING THE 2010 FBC-B
 REQUIREMENT 1015.2.1 WHERE TWO EXIT DOORS ARE REQUIRED
 . WHAT THIS DOES REQUIRE BEING USED AS A CORRIDOR
 COMPLIANCE WITH 2010 FBC-B TABLE 1018.1 ASSEMBLY
 OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN 30
 REQUIRING THE CORRIDOR TO BE A 1 HOUR FIRE RATED
 CORRIDOR, AND 3/4 HOUR FIRE RATED DOORS IN COMPLIANCE
 WITH TABLE 715.5. NOTE SHEET M-1 WOULD ALSO BE EFFECTED
 SINCE THE A/C DUCT WORK WILL BE PENETRATING FIRE RATED
 WALLS REQUIRING FIRE DAMPERS 716.3.2.1 & TABLE
 716.3.2.1.
  
 3) SHEET LS1 DOES NOT SHOW THE MEZZANINE LEVEL AND OR
 STAIRS, EMERGENCY LGHTING W/ BATTERY BACK UP, 2010
 FBC-B 1006.2.3.4.
  
 4) SHEET LS1 DOOR HARDWARE NOTE ALL DOOR HARDWARE TO BE
 LEVER TYPE. PLEASE REVIEW 2010 FBC-B 1008.1.10 PANIC
 HARDWARE REQUIRED IN ASSEMBLY OCCUPANCIES OVER 50
 OCCUPANTS.
  
 5) SHEET S-2 LIST THE PRESSURES FOR WINDOWS AND DOORS
 BUT NOT FOR THE ROOF ZONES 1, 2 & 3. 2010 FBC 1609.
 6.4.1.1. COMPONENTS & CLADDING.
  
 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS BILCO HATCH.
 (B) ROOFING PRODUCTS AND ASSEMBLIES/ A/C CURBS
 (C) PRE-ENGINEERED A/C STANDS
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) ROOFING APPROVAL FL 1046-R4 PLEASE CIRCLE WHICH
 SUB-SYSTEM TO BE INSTALLED, METHOD OF ATTACHMENT FOR
 INSULATION AS WELL AS BASE SHEET, SEE LIMITATION 5.6
 FOR ENHANCED FASTENING REQUIREMENTS.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676