2013-12-04 17:46:13 | BUILDING REVIEW APPROVED WITH PROVISO: |
| |
| 1- PROVIDE PRODUCT APPROVALS FOR: *A) HARDIBOARD FOR |
| VERTICAL APPLICATION AS SHOWN ON PLANS. ALSO, NOA |
| 08-0514.11 SUBMITTED EXPIRED ON 10/02/13. |
| **B) ENTRY DOORS AS SPECIFIED ON PLANS. (NONE |
| SUBMITTED). |
| ***C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS AND DETAILS. ONLY FLORIDA PRODUCT APPROVAL FOR |
| SIMPSON CONNECTOR H10A WAS SUBMITTED. |
| NEED PRODUCT APPROVALS FOR THE OTHER CONNECTORS |
| SPECIFIED ON PLANS AND ALL DETAILS. ***NOTE: DETAIL "B" |
| ON SHEET S3 SPECIFY "USP" CONNECTORS, NOT SIMPSON. |
| ****D) HURRICANE SHUTTERS AND COMPLETE INSTALLATION |
| SCHEDULE IF DOORS WITH GLASS DON'T HAVE IMPACT GLASS. |
| (DOOR PRODUCT APPROVAL WAS NOT SUBMITTED AT THIS TIME. |
| UNABLE TO VERIFY). |
| |
| 2- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE |
| PRODUCT APPROVALS. |
| |
| 3- TYPICAL WALL SECTION ON SHEET SHEET A4.1. VERTICAL |
| SIDING: NEED TO SHOW THE 6" CLEARANCE FROM FINISH GRADE |
| AS REQUIRED BY SEC. R704. REVISE EXTERIOR ELEVATIONS AS |
| WELL TO SHOW 6" CLEARANCE FROM THE GROUND. |
| |
| 4- ENGINEER TO PROVIDE ALL HIS INFORMATION ON THE TITLE |
| BLOCK AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. |
| ORIGINAL SUBMITTAL HAD THE INFORMATION AT THE BOTTOM OF |
| THE PAGE. THIS TIME ALL THE STRUCTURAL DRAWINGS ARE |
| MISSING THE ENGINEER'S INFORMATION. |
| |
| 5- SHEET S3: PLYWOOD SHEATHING NAILING SCHEDULE: |
| PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE |
| SPECIFIED 10D NAILS ARE EQUIVALENT OR BETTER THAN THE |
| MIN. 8D "RING SHANK" NAILS REQUIRED BY SEC. R803.2.3.1 |
| OF 2010 FBC-RESIDENTIAL AND SEC. 107.2.1.3 OF CITY |
| AMENDMENTS TO FBC. |
| |