Plan Review Notes For Permit 13080849 |
Permit Number |
13080849 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-10-21 18:48:01 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- CONDENSING UNIT PAD DETAIL STATES THAT SEE | | STRUCTURAL DRAWINGS FOR SPECIFICATIONS. STRUCTURAL | | DRAWINGS DON'T PROVIDE ANY SPECIFICATIONS. PROVIDE SUCH | | SPECIFICATIONS. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | 2- MECHANICAL PLAN ON SHEET A5.1 SHOWS THE RETURN AIR | | FROM THE BEDROOMS BUT IT DOESN'T SHOW RETURN AIR FOR | | THE REST OF THE HOUSE. SHOW HOW PROVIDING THE RETURN | | AIR FOR THE REST OF THE HOUSE. SEC. M1602 OF 2010 | | FBC-RESIDENTIAL. | | | | 3- PROVIDE THE COMPLETE EQUIPMENT SIZING CALCULATIONS | | NOT JUST THE SUMMARY. AND, INCLUDE THE EQUIPMENT AS | | REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | ***NOTE: COORDINATE WITH THE ENERGY CALCULATIONS | | SUBMITTED. | | | | 4- A/C PLAN ON SHEET A5.1 TO SHOW EQUIPMENT LISTED IN | | THE EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 OF 2010 | | FBC-ENERGY CONSERVATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|