2013-08-28 12:35:23 | 223 CLEMATIS STREET | | PERMIT #13080811 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SHEET A-1: THE LIQUOR ROOM (#101) DOOR OBSTRUCTS | | EGRESS. PER NFPA 101 SECTION 7.2.1.4.3 DOOR LEAF | | ENCROACHMENT - DURING ITS SWING, ANY DOOR LEAF IN A | | MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF | | THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A | | PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL PROJECT | | NOT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH OF AN | | AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, WHEN | | FULLY OPEN. | | | | SHEET A-1: CORRIDOR #105 AND #108 SHALL BE PERMANENTLY | | IDENTIFIED WITH SIGNAGE OR STENCILING INDICATING "EXIT | | ACCESS - NO STORAGE PERMITTED." | | | | SHEET E3.1: NEW WING WALL BY COOLER (#114) OBSTRUCTS | | FIRE ALARM SIGNALING APPLIANCE. ADDITIONAL FIRE ALARM | | NOTIFICATION APPLIANCES WILL BE NEEDED IN THE MAIN | | DINING AREA (#100). | | | | SHEET E3.1: NO EXISTING FIRE ALARM NOTIFICATION | | APPLIANCES INDICATED IN MENS' RESTROOM #102, WOMENS' | | RESTROOM #103, CORRIDOR #105 OR CORRIDOR #108. DEVICES | | WILL BE NEEDED IF NOT ALREADY EXISTING. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|