2013-08-28 12:35:23223 CLEMATIS STREET
 PERMIT #13080811
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-1: THE LIQUOR ROOM (#101) DOOR OBSTRUCTS
 EGRESS. PER NFPA 101 SECTION 7.2.1.4.3 DOOR LEAF
 ENCROACHMENT - DURING ITS SWING, ANY DOOR LEAF IN A
 MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF
 THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A
 PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND SHALL PROJECT
 NOT MORE THAN 7-INCHES INTO THE REQUIRED WIDTH OF AN
 AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, WHEN
 FULLY OPEN.
  
 SHEET A-1: CORRIDOR #105 AND #108 SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNAGE OR STENCILING INDICATING "EXIT
 ACCESS - NO STORAGE PERMITTED."
  
 SHEET E3.1: NEW WING WALL BY COOLER (#114) OBSTRUCTS
 FIRE ALARM SIGNALING APPLIANCE. ADDITIONAL FIRE ALARM
 NOTIFICATION APPLIANCES WILL BE NEEDED IN THE MAIN
 DINING AREA (#100).
  
 SHEET E3.1: NO EXISTING FIRE ALARM NOTIFICATION
 APPLIANCES INDICATED IN MENS' RESTROOM #102, WOMENS'
 RESTROOM #103, CORRIDOR #105 OR CORRIDOR #108. DEVICES
 WILL BE NEEDED IF NOT ALREADY EXISTING.
  