2013-09-19 16:52:37 | 513 CLEMATIS STREET |
| PERMIT #13080797 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NOTE: THE SECOND FLOOR HAS BOTH AN INSIDE EGRESS STAIR |
| AND AN EXTERIOR STAIR; HOWEVER, THE STAIRS ARE NOT |
| SEPARATED BY AT LEAST 42 FEET (84 FOOT DIAGONAL/ 2 = 42 |
| FEET [WORST CASE] OR 64 FOOT DIAGONAL/ 2 = 32 FEET |
| [BEST CASE]) TO BE CONSIDERED TWO SEPARATE EXITS. NEW |
| BUSINESS OCCUPANCIES ARE PERMITTED ONE EXIT PER NFPA |
| 101 SECTION 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED |
| FOR A ROOM OR AREA WITH A TOTAL OCCUPANT LOAD OF FEWER |
| THAN 100 PERSONS WHEN A SINGLE OUTSIDE STAIR IN |
| ACCORDANCE WITH 7.2.2 IS INSTALLED AND WILL SERVE ALL |
| FLOORS PERMITTED WITHIN THE 15 FEET VERTICAL TRAVEL |
| LIMITATION. |
| |
| NONE OF THE DOORS AND WINDOWS ADJACENT TO THE EXTERIOR |
| STAIRS ARE PROTECTED. PER NFPA 101 SECTION 7.2.2.6.3 |
| "SEPARATION AND PROTECTION OF OUTSIDE STAIRS: OUTSIDE |
| STAIRS SHALL BE SEPARATED FROM THE INTERIOR OF THE |
| BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE |
| RATING REQUIRED FOR ENCLOSED STAIRS WITH FIXED OR |
| SELF-CLOSING OPENING PROTECTIVES." WALL CONSTRUCTION |
| SHALL EXTEND AS FOLLOWS: (1) VERTICALLY FROM THE |
| FINISHED GROUND LEVEL TO A POINT 10 FEET ABOVE THE |
| TOPMOST LANDING OF THE STAIRS OR TO THE ROOFLINE, |
| WHICHEVER IS LOWER (2) HORIZONTALLY FOR NOT LESS THAN |
| 10 FEET. PER NFPA 101 SECTION 7.2.2.6.4 "PROTECTION OF |
| OPENINGS: ALL OPENINGS BELOW AN OUTSIDE STAIR SHALL BE |
| PROTECTED WITH AN ASSEMBLY HAVING A MINIMUM 45-MINUTE |
| FIRE PROTECTION RATING." |
| |
| PLANS DO NOT INDICATE WHERE THE EXTERIOR STAIR |
| DISCHARGES TO. PER NFPA 101 SECTION 7.7.1 EXITS SHALL |
| DISCHARGE OR LEAD TO A STREET, ALLEY, PUBLIC WAY, ETC. |
| |
| PLANS DO NOT INDICATE IF ANY OF THE TENANT SPACES ARE |
| FIRE SEPARATED. |
| |