2013-09-24 12:43:52BUILDING PLAN REVIEW
 PERMIT: 13080797
 ADD: 513 CLEMATIS ST UNITS # 201, 203, & 205
 CONT: LARRY B. ROWE
 TEL: (561)835-17999
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:SEPT 24/ 2013
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION.107.3.5.1.1. MINIMUM CRITERIA FOR COMMERCIAL
 PLAN REVIEW:
 2A) MINIMUM BUILDING TYPE
 2B)COMPLIED
 2C) COMPLIED.
 2D) SEMI-COMPLIED.
 2D)(1) LIFE SAFETY PLAN THE SECOND STORY IS SHOWN, BUT
 THE JOBSITE VISIT SHOWED THE BACK EXTERIOR STAIR WAY
 LEADING INTO A COURTYARD WITH NO EXIT. MAKING THIS A
 SINGLE EXIT FROM THE FRONT SET OF STAIRS. FBC-B TABLE
 1021.2 STORIES WITH ONE- EXIT TRAVEL DISTANCE LIMIT 75
 FEET. THE COURTYARD WILL NEED TO LEED TO A PUBLIC WAY.
 AT THE JOBSITE VISIT THE CONTRACTOR AND OWNER INDICATED
 ON THE WEST SIDE OF THE BUILDING WHERE THEY WERE GOING
 TO OPEN FRONTAGE TO CLEMATIS ST FOR THE SECOND MEANS OF
 EGRESS TO THE PUBLIC WAY, ALSO REVIEW FBC-B 1027.5
 EGRESS COURT REQUIREMENTS. PLEASE PROVIDE A SITE PLAN
 WITH THE EGRESS FOR THE BACK EXTERIOR STAIR THRU THE
 COURTYARD LEADING TO THE PUBLIC WAY.
  
 2D)(2)SEMI-COMPLIED.9/26/13 SUBMITTED 45 MINUTE RATED
 GLASS BLOCK FOR WINDOWS WITHIN 10' OF EXTERIOR STIAR.
 THE SECOND ISSUE WHEN THE EGRESS FROM THE COURTYARD TO
 THE PUBLIC WAY OCCURS IS THE DISTANCE BETWEEN THE TOP
 OF THE 2 STAIRWAYS IS NOT 1/2 THE OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 DIAGONAL DISTANCE PER FBC-B 1015.2.1. NOTE WHEN YOU
 FIGURE THE OVERALL DIAGONAL OF THE BUILDING WITHOUT THE
 TERRRACE WE ARE WITHIN ONE FOOT OF COMPLIANCE. AT SOME
 TIME SOMEONE HAS CUT IN A EXTERIOR DOORWAY AND CREATED
 A ROOF TOP TERRACE MAKING THE OVER ALL DIAGONAL
 DISTANCE A GREATER DISTANCE FOR THE STAIRS TO BE APART,
 AND NOT CODE COMPLIANT.
  
 EVEN IF YOU LOOK AT UNIT 203 THE FURTHEST POINT ON THE
 TERRACE THE TRAVEL DISTANCE TO THE BOTTOM OF THE STAIRS
 IS OVER 75 FEET. THE FURTHEST DISTANCE FROM THE
 FURTHEST POINT ON THE TERRACE TO THE TOP LANDING AT THE
 BACK STAIR IS APPROX. 68 FEET, OUTSIDE OF THE BUILDING
 THE BUILDING OFFICIAL WILL APPROVE THIS DISTANCE BUT
 THE BATHROOM WINDOW IN UNIT DOES NEED TO BE 3/4 HOUR
 FIRE RATED, IT IS WITHIN 10 FEET OF THE EXTERIOR STAIR,
 FBC-B 1026.6 AND THE EXTERIOR DOOR WILL NEED TO BE 1
 HOUR FIRE RATED.
  
 3) LIFE SAFETY PLAN SHALL INCLUDE THE FOLLOWING
 INFORMATION:
 3A COMPLIED.
 3B) COURTYARD 2010 FBC-B 1027.5.
 3C) STAIRWELL WALL RATINGS, 2010 FBC-B 1022.1, & 2010
 EXISTING BUILDING CODE 912.5.3 EXCEPTION.
 3D) 2010 EXISTING BUILDING CODE 912.4.4. HANDRAILS
 SHALL COMPLY WITH 705.9 IN AREAS OF CHANGE OF
 OCCUPANCY. HANDRAILS SHALL BE THE FULL LENGTH OF THE
 RUN OF THE STEPS ON AT LEAST ONE SIDE.
 3E) 2010 EXISTING BUILDING CODE 912.8 ACCESSIBILITY.
 3F) 2010 FBC-ACCESSIBILITY CODE 202.4.1
 DISPROPORTIONATE COST.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  