2013-08-28 11:18:05 | 513 CLEMATIS STREET | | PERMIT #13080797 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE PERMIT APPLICATION INDICATES A CHANGE OF OCCUPANCY | | FROM RESIDENTIAL TO COMMERCIAL; HOWEVER, THE PLANS DO | | NOT INDICATE THE INTENDED COMMERCIAL OCCUPANCY | | (BUSINESS, MERCANTILE, ETC.) | | | | PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES, | | OCCUPANT LOADS, FIRE RATED WALLS, FIRE RATE DOORS, EXIT | | SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON | | PATH OF TRAVEL ETC. | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE PERFORMED | | AT THIS TIME. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|