Plan Review Notes
Plan Review Notes For Permit 13080729
Permit Number 13080729
Review Stop E
Sequence Number 1
Notes
Date Text
2013-09-25 17:17:34FIRST REVIEW - 9-25-13
 1. PLEASE SHOW CIRCUIT NUMBERS ON FLOOR PLAN
 2. ALL NEW CIRCUITS TO BE AFCI PROTECTED. POWER AND
 LIGHTING. NEC 210.12.B
 3. WHIRLPOOL TUB MUST BE BONDED WITH MINIMUM #8 WIRE
 NEC 680.74
 4. ALL RECPTACLES WITHIN 6 FT OF SINKS MUST BE GFCI NEC
 210.8
 VB