Plan Review Notes For Permit 13080729 |
Permit Number |
13080729 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-09-25 17:17:34 | FIRST REVIEW - 9-25-13 | | 1. PLEASE SHOW CIRCUIT NUMBERS ON FLOOR PLAN | | 2. ALL NEW CIRCUITS TO BE AFCI PROTECTED. POWER AND | | LIGHTING. NEC 210.12.B | | 3. WHIRLPOOL TUB MUST BE BONDED WITH MINIMUM #8 WIRE | | NEC 680.74 | | 4. ALL RECPTACLES WITHIN 6 FT OF SINKS MUST BE GFCI NEC | | 210.8 | | VB |
|