2013-12-30 16:48:11THIS ELECTRICAL REVIEW WAS CONDITIONALLY APPROVED AS
 MARKED BELOW AND ON APPROVED PLANS:
 1. THE ELECTRICAL OUTLET SPACING DOES NOT APPEAR TO
 MEET THE REQUIREMENTS OF NEC 210.52.
 2. THE SMOKE AND/OR CARBON MONOXIDE DETECTORS ARE NOT
 PROPERLY SITUATED. INSTALL THE APPLICABLE DETECTOR
 ACCORDING TO MANUFACTURER'S INSTRUCTIONS FOLLOWING THE
 REQUIREMENTS OF THE FBC-R 314 & 315 ALONG WITH THE
 PLACEMENT GUIDE LINES OF THE NFPA 29.8.3.4
 3. EACH UNIT SHALL HAVE ITS INDIVIDUAL INTER-SYSTEM
 BONDING TERMINAL AS PER NEC 250.94
  
 ALL WORK IS SUBJECT TO THE FIELD INSPECTOR'S APPROVAL