Plan Review Notes For Permit 13080662 |
Permit Number |
13080662 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-12-30 16:48:11 | THIS ELECTRICAL REVIEW WAS CONDITIONALLY APPROVED AS | | MARKED BELOW AND ON APPROVED PLANS: | | 1. THE ELECTRICAL OUTLET SPACING DOES NOT APPEAR TO | | MEET THE REQUIREMENTS OF NEC 210.52. | | 2. THE SMOKE AND/OR CARBON MONOXIDE DETECTORS ARE NOT | | PROPERLY SITUATED. INSTALL THE APPLICABLE DETECTOR | | ACCORDING TO MANUFACTURER'S INSTRUCTIONS FOLLOWING THE | | REQUIREMENTS OF THE FBC-R 314 & 315 ALONG WITH THE | | PLACEMENT GUIDE LINES OF THE NFPA 29.8.3.4 | | 3. EACH UNIT SHALL HAVE ITS INDIVIDUAL INTER-SYSTEM | | BONDING TERMINAL AS PER NEC 250.94 | | | | ALL WORK IS SUBJECT TO THE FIELD INSPECTOR'S APPROVAL |
|