Plan Review Notes For Permit 13080650 |
Permit Number |
13080650 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-01-06 16:16:36 | VILLAS ON ANTIQUE ROW, BLDG. 5 | | ELECTRICAL PLAN REVIEW NOTES FOR PERMITS: 13080647, | | 13080648, 13080649, 13080650, 13080651, 13080653 AND | | 13080654 | | | | THE FOLLOWING NOTES ARE BASICALLY APPLICABLE TO ALL | | SEVEN (7) UNITS ALONG WITH THEIR SUBSEQUENT PERMIT | | NUMBERS AS DESCRIBED ABOVE: | | NOTE: THERE IS A CONFLICT IN THE UNIT DESIGNATIONS AS | | INDICATED ON THE ARCHITECTURAL DRAWINGS AND THE FIRE | | PROTECTION DRAWINGS. | | MOST OF THE ITEMS PREVIOUSLY ADDRESSED HAVE BEEN | | CORRECTED EXCEPT THE FOLLOWING: | | | | 1. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE SIZED AS | | PER NEC 250.66 FOR FOUR (4) 350 KCMILS AL | | 2. NOTE 2 ADDRESSING THE SMOKE/CARBON MONOXIDE | | DETECTORS IS INCORRECT. THE DEVICES ARE TO BE | | INTER-CONNECTED WITHIN THE UNIT, BUT AT NO TIME TIED IN | | TO THE FIRE ALARM SYSTEM. NONE OF THE NOTES MENTION THE | | INSTALLATION TO BE AS PER MANUFACTURER?S INSTRUCTIONS. | | (NOTE: THE USE OF COMBINATION SMOKE/CO DETECTORS AND | | FOLLOWING PROPER PLACEMENT MAY REDUCE THE NUMBER OF | | DEVICES REQUIRED FOR COMPLIANCE) | | 3. AFTER LOOKING THROUGH THE ENTIRE SET, I FOUND THE | | REFERENCES TO THE EASEMENT ON PAGE 2.1 OF THE UNITS, | | BUT PAGE E1.1 FOR THE SKY END UNIT HAS YET TO BE | | CORRECTED. | | | | |
|