2014-01-06 16:16:36VILLAS ON ANTIQUE ROW, BLDG. 5
 ELECTRICAL PLAN REVIEW NOTES FOR PERMITS: 13080647,
 13080648, 13080649, 13080650, 13080651, 13080653 AND
 13080654
  
 THE FOLLOWING NOTES ARE BASICALLY APPLICABLE TO ALL
 SEVEN (7) UNITS ALONG WITH THEIR SUBSEQUENT PERMIT
 NUMBERS AS DESCRIBED ABOVE:
 NOTE: THERE IS A CONFLICT IN THE UNIT DESIGNATIONS AS
 INDICATED ON THE ARCHITECTURAL DRAWINGS AND THE FIRE
 PROTECTION DRAWINGS.
 MOST OF THE ITEMS PREVIOUSLY ADDRESSED HAVE BEEN
 CORRECTED EXCEPT THE FOLLOWING:
  
 1. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE SIZED AS
 PER NEC 250.66 FOR FOUR (4) 350 KCMILS AL
 2. NOTE 2 ADDRESSING THE SMOKE/CARBON MONOXIDE
 DETECTORS IS INCORRECT. THE DEVICES ARE TO BE
 INTER-CONNECTED WITHIN THE UNIT, BUT AT NO TIME TIED IN
 TO THE FIRE ALARM SYSTEM. NONE OF THE NOTES MENTION THE
 INSTALLATION TO BE AS PER MANUFACTURER?S INSTRUCTIONS.
 (NOTE: THE USE OF COMBINATION SMOKE/CO DETECTORS AND
 FOLLOWING PROPER PLACEMENT MAY REDUCE THE NUMBER OF
 DEVICES REQUIRED FOR COMPLIANCE)
 3. AFTER LOOKING THROUGH THE ENTIRE SET, I FOUND THE
 REFERENCES TO THE EASEMENT ON PAGE 2.1 OF THE UNITS,
 BUT PAGE E1.1 FOR THE SKY END UNIT HAS YET TO BE
 CORRECTED.
  
  