2013-08-17 12:56:03 | BUILDING/ PLUMBING PLAN REVIEW |
| PERMIT: 13080619 |
| ADD: 255 EVERNIA SUITE # 1507 |
| CONT: CREATIVE HOMEWORKS |
| TEL: (561)506-4466 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: AUGUST 17/2013 |
| ACTION: PROVISO |
| PLUMBING PROVISO: |
| |
| 2010 FBC-P 417.5.2 SHOWER LINING. FLOORS UNDER SHOWER |
| COMPARTMENTS, SUCH LINERS SHALL TURN UP ON ALL SIDES AT |
| LEAST 2 INCHES (51 MM) ABOVE THE FINISHED THRESHOLD |
| LEVEL. LINERS SHALL BE RECESSED AND FASTENED TO AN |
| APPROVED BACKING SO AS NOT TO OCCUPY THE SPACE REQUIRED |
| FOR WALL COVERING, AND SHALL NOT BE NAILED OR |
| PERFORATED AT ANY POINT LESS THAN 1 INCH (25 MM) ABOVE |
| THE FINISHED THRESHOLD. LINERS SHALL BE PITCHED |
| ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE |
| FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE |
| OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT |
| JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED |
| LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |