Plan Review Notes
Plan Review Notes For Permit 13080554
Permit Number 13080554
Review Stop B
Sequence Number 1
Notes
Date Text
2013-08-20 07:56:45BUILDING PLAN REVIEW
 PERMIT: 13080554
 ADD: 1400 CENTREPARK BLVD, SUITE # 1000
 CONT: CHANDLER CONSTRUCTION
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY AUGUST 20/ 2013
  
 ACTION: PROVISO REVISION REQUIRED
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) NEITHER SHEET A2 FLOOR/ CEILING PLAN, A4 LIFE SAFETY
 PLAN NOR E2.1 LIGHTING PLAN SHOW COMPLIANCE WITH:
 1A) 2010 FBC-B 1006.3.7
 WHERE EMERGENCY LIGHTING FACILITIES ARE REQUIRED BY
 SECTION 1006.2, THE EXIT SIGNS SHALL BE ILLUMINATED BY
 THE EMERGENCY LIGHTING FACILITIES. THE LEVEL OF
 ILLUMINATION OF THE EXIT SIGN SHALL BE AT THE LEVELS
 PROVIDED IN ACCORDANCE WITH SECTION 1006.3.5 FOR THE
 REQUIRED EMERGENCY LIGHTING TIME DURATION AS SPECIFIED
 IN SECTION 1006.2.3.1, BUT SHALL BE PERMITTED TO
 DECLINE TO 60 PERCENT OF THE ILLUMINATION LEVEL AT THE
 END OF THE EMERGENCY LIGHTING TIME DURATION.
  
 1B) 2010 FBC-B 1006.3.8
 WHERE THE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT
 IS NOT APPARENT, A DIRECTIONAL SIGN COMPLYING WITH
 SECTIONS 1006.3.5 OR 1006.3.6 READING ?EXIT,? OR A
 SIMILAR DESIGNATION WITH A DIRECTIONAL INDICATOR
 SHOWING THE DIRECTION OF TRAVEL SHALL BE PLACED IN
 EVERY LOCATION. DIRECTIONAL SIGNS SHALL BE LISTED.
  
 C) 2010 FBC-B 1006.3.4 EXIT STAIR DOOR OR TACTILE
 SIGNAGE.
 TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH
 ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.
  
 D) 2010 FBC-B 1006.3.3
 EVERY REQUIRED SIGN SHALL BE LOCATED AND OF SUCH SIZE,
 DISTINCTIVE COLOR AND DESIGN AS TO BE READILY VISIBLE
 AND SHALL PROVIDE CONTRAST WITH INTERIOR FINISH OR
 OTHER SIGNS. NO EQUIPMENT THAT IMPAIRS VISIBILITY OF AN
 EXIT SIGN SHALL BE PERMITTED, NOR SHALL THERE BE ANY
 BRIGHTLY ILLUMINATED SIGN OR OBJECT IN OR NEAR THE LINE
 OF VISION OF THE REQUIRED EXIT SIGN OF SUCH A CHARACTER
 AS TO DETRACT ATTENTION FROM THE EXIT SIGN.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  