2013-08-20 07:56:45 | BUILDING PLAN REVIEW |
| PERMIT: 13080554 |
| ADD: 1400 CENTREPARK BLVD, SUITE # 1000 |
| CONT: CHANDLER CONSTRUCTION |
| TEL: (561)791-6934 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUESDAY AUGUST 20/ 2013 |
| |
| ACTION: PROVISO REVISION REQUIRED |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| 1) NEITHER SHEET A2 FLOOR/ CEILING PLAN, A4 LIFE SAFETY |
| PLAN NOR E2.1 LIGHTING PLAN SHOW COMPLIANCE WITH: |
| 1A) 2010 FBC-B 1006.3.7 |
| WHERE EMERGENCY LIGHTING FACILITIES ARE REQUIRED BY |
| SECTION 1006.2, THE EXIT SIGNS SHALL BE ILLUMINATED BY |
| THE EMERGENCY LIGHTING FACILITIES. THE LEVEL OF |
| ILLUMINATION OF THE EXIT SIGN SHALL BE AT THE LEVELS |
| PROVIDED IN ACCORDANCE WITH SECTION 1006.3.5 FOR THE |
| REQUIRED EMERGENCY LIGHTING TIME DURATION AS SPECIFIED |
| IN SECTION 1006.2.3.1, BUT SHALL BE PERMITTED TO |
| DECLINE TO 60 PERCENT OF THE ILLUMINATION LEVEL AT THE |
| END OF THE EMERGENCY LIGHTING TIME DURATION. |
| |
| 1B) 2010 FBC-B 1006.3.8 |
| WHERE THE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT |
| IS NOT APPARENT, A DIRECTIONAL SIGN COMPLYING WITH |
| SECTIONS 1006.3.5 OR 1006.3.6 READING ?EXIT,? OR A |
| SIMILAR DESIGNATION WITH A DIRECTIONAL INDICATOR |
| SHOWING THE DIRECTION OF TRAVEL SHALL BE PLACED IN |
| EVERY LOCATION. DIRECTIONAL SIGNS SHALL BE LISTED. |
| |
| C) 2010 FBC-B 1006.3.4 EXIT STAIR DOOR OR TACTILE |
| SIGNAGE. |
| TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH |
| ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR |
| ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL |
| BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60 |
| INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER |
| LINE OF THE SIGN. |
| |
| D) 2010 FBC-B 1006.3.3 |
| EVERY REQUIRED SIGN SHALL BE LOCATED AND OF SUCH SIZE, |
| DISTINCTIVE COLOR AND DESIGN AS TO BE READILY VISIBLE |
| AND SHALL PROVIDE CONTRAST WITH INTERIOR FINISH OR |
| OTHER SIGNS. NO EQUIPMENT THAT IMPAIRS VISIBILITY OF AN |
| EXIT SIGN SHALL BE PERMITTED, NOR SHALL THERE BE ANY |
| BRIGHTLY ILLUMINATED SIGN OR OBJECT IN OR NEAR THE LINE |
| OF VISION OF THE REQUIRED EXIT SIGN OF SUCH A CHARACTER |
| AS TO DETRACT ATTENTION FROM THE EXIT SIGN. |
| |