Plan Review Notes For Permit 13080531 |
Permit Number |
13080531 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-09-03 17:13:50 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FROM PREVIOUS LIST: | | | | 1. OK | | | | 2. INDICATE WHICH FASTENING METHOD IS PROPOSED FOR THE | | FLAT DECK ON THE ENGINEERING PROVIDED. | | | | 2ND REVIEW, A ROOFING FORM WAS SUBMITTED BUT FASTENING | | PROPOSED DOES NOT COMPLY WITH THE NOA FOR ZONE 1 OR FOR | | THE ENGINEERING FOR ZONES 2 AND 3. INDICATE FASTENING | | METHOD ON THE ENGINEERING OR PROVIDE SIGNED AND SEALED | | ORIGINAL ENGINEERING OR REVISE ROOFING FORM 100 TO BE | | CONSISTENT WITH ENGINEERING. | | | | 3. OK | | | | NEW COMMENT: TWO SETS OF ALL DOCUMENTS REQUIRED. ONLY | | ONE ROOFING FORM PROVIDED. | | |
|