Plan Review Notes
Plan Review Notes For Permit 13080523
Permit Number 13080523
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-23 07:12:42SEE NOTES ON PLANS
  
 18.4.1.3* SOUND FROM NORMAL OR PERMANENT SOURCES,
 HAVING A DURATION GREATER THAN 60 SECONDS, SHALL BE
 INCLUDED WHEN MEASURING MAXIMUM AMBIENT SOUND LEVEL.
 SOUND FROM TEMPORARY OR ABNORMAL SOURCES SHALL NOT BE
 REQUIRED TO BE INCLUDED WHEN MEASURING MAXIMUM AMBIENT
 SOUND LEVEL.
  
  
 18.4.1.4 AUDIBLE NOTIFICATION APPLIANCES FOR ALERT AND
 EVACUATION SIGNAL TONES SHALL MEET THE REQUIREMENTS OF
 18.4.3 (PUBLIC MODE AUDIBLE REQUIREMENTS), 18.4.4
 (PRIVATE MODE AUDIBLE REQUIREMENTS), 18.4.5 (SLEEPING
 AREA REQUIREMENTS), OR 18.4.6 (NARROW BAND TONE
 SIGNALING FOR EXCEEDING MASKED THRESHOLDS), AS
 APPLICABLE.
  
 18.4.3* PUBLIC MODE AUDIBLE REQUIREMENTS.
  
 18.4.3.1* TO ENSURE THAT AUDIBLE PUBLIC MODE SIGNALS
 ARE CLEARLY HEARD, UNLESS OTHERWISE PERMITTED BY
 18.4.3.2 THROUGH 18.4.3.5, THEY SHALL HAVE A SOUND
 LEVEL AT LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND
 LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL HAVING A
 DURATION OF AT LEAST 60 SECONDS, WHICHEVER IS GREATER,
 MEASURED 5 FT (1.5 M) ABOVE THE FLOOR IN THE AREA
 REQUIRED TO BE SERVED BY THE SYSTEM USING THE
 A-WEIGHTED SCALE (DBA).
  
  
  
  