2013-10-21 08:02:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 FBC 2010 EXISTING BUILDING CODE, CHAPTER 10 ADDITIONS:
  
 1. REVISE PLAN TO SHOW THE AREA OF THE EXISTING
 BUILDING, BUILDING TYPE (FBC CHAPTER 6), AND OCCUPANCY
 CLASSIFICATION (FBC CHAPTER 3).
  
 2ND REVIEW -
  
 EXISTING BUILDING IS SHOWN AS TYPE IV, SPRINKLERED.
 TYPE IV IS HEAVY TIMBER - AERIALS SHOW THIS AS A
 QUONSET HUT, WHICH IS TYPICALLY STEEL. PLEASE PROVIDE
 INFORMATION TO SHOW HOW IT HAS BEEN DETERMINED THAT
 THIS IS A HEAVY TIMBER BUILDING.
  
 2. REVISE PLAN TO SHOW THE BUILDING TYPE OF THE
 PROPOSED NEW STRUCTURE (FBC CHAPTER 6).
  
 TYPE IIB IS SHOWN AS PROPOSED NEW CONSTRUCTION. FOAM IS
 NOT TYPICALLY CONSIDERED NON COMBUSTIBLE. PROVIDE DATA
 TO SHOW THAT THE FOAM PANELS ARE NON COMBUSTIBLE.
  
 3. REVISE PLAN TO SHOW COMPLIANCE WITH FBC TABLE 601,
 BUILDING HEIGHT AND AREA (EXISTING BUILDING PLUS
 ADDITION).
  
 BUILDING IS NOTED AS SPRINKLERED, BUT IF SPRINKLERS ARE
 REQUIRED FOR THIS BUILDING TO COMPLY WITH FBC TABLE
 503, SPRINKLERS WOULD BE REQUIRED FOR THE ADDITION.
  
 **NEW COMMENT**
  
 4. PLEASE SEE FBC TABLE 503 AND 601. IT APPEARS THAT
 THE EXISTING STRUCTURE AND THE PROPOSED ADDITION MAY BE
 TYPE VB CONSTRUCTION. SEE FBC 506.2, AREA INCREASES MAY
 APPLY. PLEASE REVISE PLANS TO SHOW COMPLIANCE WITH
 ABOVE CITED CODE SECTIONS.
  