2013-10-21 08:02:48 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FROM PREVIOUS LIST: |
| |
| FBC 2010 EXISTING BUILDING CODE, CHAPTER 10 ADDITIONS: |
| |
| 1. REVISE PLAN TO SHOW THE AREA OF THE EXISTING |
| BUILDING, BUILDING TYPE (FBC CHAPTER 6), AND OCCUPANCY |
| CLASSIFICATION (FBC CHAPTER 3). |
| |
| 2ND REVIEW - |
| |
| EXISTING BUILDING IS SHOWN AS TYPE IV, SPRINKLERED. |
| TYPE IV IS HEAVY TIMBER - AERIALS SHOW THIS AS A |
| QUONSET HUT, WHICH IS TYPICALLY STEEL. PLEASE PROVIDE |
| INFORMATION TO SHOW HOW IT HAS BEEN DETERMINED THAT |
| THIS IS A HEAVY TIMBER BUILDING. |
| |
| 2. REVISE PLAN TO SHOW THE BUILDING TYPE OF THE |
| PROPOSED NEW STRUCTURE (FBC CHAPTER 6). |
| |
| TYPE IIB IS SHOWN AS PROPOSED NEW CONSTRUCTION. FOAM IS |
| NOT TYPICALLY CONSIDERED NON COMBUSTIBLE. PROVIDE DATA |
| TO SHOW THAT THE FOAM PANELS ARE NON COMBUSTIBLE. |
| |
| 3. REVISE PLAN TO SHOW COMPLIANCE WITH FBC TABLE 601, |
| BUILDING HEIGHT AND AREA (EXISTING BUILDING PLUS |
| ADDITION). |
| |
| BUILDING IS NOTED AS SPRINKLERED, BUT IF SPRINKLERS ARE |
| REQUIRED FOR THIS BUILDING TO COMPLY WITH FBC TABLE |
| 503, SPRINKLERS WOULD BE REQUIRED FOR THE ADDITION. |
| |
| **NEW COMMENT** |
| |
| 4. PLEASE SEE FBC TABLE 503 AND 601. IT APPEARS THAT |
| THE EXISTING STRUCTURE AND THE PROPOSED ADDITION MAY BE |
| TYPE VB CONSTRUCTION. SEE FBC 506.2, AREA INCREASES MAY |
| APPLY. PLEASE REVISE PLANS TO SHOW COMPLIANCE WITH |
| ABOVE CITED CODE SECTIONS. |
| |