Plan Review Notes For Permit 13080496 |
Permit Number |
13080496 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-01-28 14:51:01 | MECHANICAL REVIEW SECOND CHECKLIST. | | CODE: 2010 FBC. | | | | | | 1- FLOOR PLAN LAYOUT SHOWN ON PLANS SUBMITTED DON'T | | MATCH FLOOR PLAN LAYOUT APPROVED FOR MASTER #13041122. | | SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | 2- PROVIDE COMPLETE AND CLEAR SPECIFICATIONS FOR THE | | ATTACHMENT OF THE CONDENSING UNIT TO THE CONCRETE SLAB. | | SPECIFY THE STRAP SIZE AND HOW ARE THE THREE #14 SCREWS | | INSTALLED AS SPECIFIED ON CURRENT DETAIL. REQUIRED BY | | SEC. M1307.2.1 OF 2010 FBC-RESIDENTIAL. (REPEAT | | COMMENT. NOT ADDRESSED). ENGINEER IS ONLY STATING | | "SECURE CONDENSING UNIT TO CONCRETE PAD IN ACCORDANCE | | WITH FMC 9RESIDENTIAL) SECTION 1307.3.1". THIS RESPONSE | | DOESN'T ADDRESS HOW THE UNIT IS ATTACHED TO THE | | CONCRETE SLAB. THE ENGINEER OF RECORD IS THE ONE WHO | | DESIGNS HOW IS THE UNIT ATTACHED TO THE CONCRETE SLAB | | TO RESIST THE WIND LOADS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|