2013-08-16 10:37:55 | RESIDENTIAL (R3) RENOVATION, MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- RETURN AIR CAN'T BE TAKEN FROM THE KITCHEN. SEC. | | M1602.2 OF 2010 FBC-RESIDENTIAL. | | | | 2- PROVIDE 2 COPIES OF PLANS WITH ENGINEER'S ORIGINAL | | SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA | | STATUTE. | | | | 3- PROVIDE COMPLETE AND CLEAR SPECIFICATIONS FOR THE | | ATTACHMENT OF THE CONDENSING UNIT TO THE CONCRETE SLAB. | | SPECIFY THE STRAP SIZE AND HOW ARE THE THREE #14 SCREWS | | INSTALLED AS SPECIFIED ON CURRENT DETAIL. SEC. | | M1307.2.1 OF 2010 FBC-RESIDENTIAL. | | | | 4- NEED A/C CONTRACTOR TO APPLY FOR THE MECHANICAL | | PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|