Plan Review Notes
Plan Review Notes For Permit 13080496
Permit Number 13080496
Review Stop M
Sequence Number 1
Notes
Date Text
2013-08-16 10:37:55RESIDENTIAL (R3) RENOVATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- RETURN AIR CAN'T BE TAKEN FROM THE KITCHEN. SEC.
 M1602.2 OF 2010 FBC-RESIDENTIAL.
  
 2- PROVIDE 2 COPIES OF PLANS WITH ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE.
  
 3- PROVIDE COMPLETE AND CLEAR SPECIFICATIONS FOR THE
 ATTACHMENT OF THE CONDENSING UNIT TO THE CONCRETE SLAB.
 SPECIFY THE STRAP SIZE AND HOW ARE THE THREE #14 SCREWS
 INSTALLED AS SPECIFIED ON CURRENT DETAIL. SEC.
 M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 4- NEED A/C CONTRACTOR TO APPLY FOR THE MECHANICAL
 PERMIT.
  
  