2013-08-21 07:31:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FBC 1609, SPECIFICATION FOR FASTENING CANNOT BE "AS | | NEEDED." GRAPHICALLY THREE FASTENERS TOP AND BOTTOM ARE | | SHOWN FOR A 30' SPAN. IF PLANS ARE NOT PREPARED BY A | | DESIGN PROFESSIONAL, PROVIDE CALCULATIONS TO SHOW HOW | | THIS WILL RESIST WIND LOADS. | | | | 2. REVISE PLAN TO INCLUDE WIND DESIGN CRITIERA FBC | | 1603.4.1. | | | | 3. IF PLANS ARE PREPARED BY A DESIGN PROFESSIONAL | | (ARCHITECT OR ENGINEER), TITLE BLOCK REQUIRED FS | | 471,481. IF PLANS ARE PREPARED BY SOMEONE OTHER THAN A | | DESIGN PROFESSIONAL, THE PLANS WILL INCLUDE THE PRINTED | | NAME AND SIGNATURE OF THE INDIVIDUAL TAKING | | RESPONSIBILITY FOR THE DESIGN FBC 107. | | |
|