Plan Review Notes
Plan Review Notes For Permit 13080459
Permit Number 13080459
Review Stop B
Sequence Number 2
Notes
Date Text
2013-10-19 11:26:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LISTS:
  
 1. INSTALLATION SCHEDULE IS INCOMPLETE. SHUTTER
 MOUNTING CONNECTION TYPE, ANCHOR SPACING, SUBSTRATE NOT
 COMPLETED
  
 2ND REVIEW, THIS INFORMATION NOT PROVIDED. SHUTTER
 MOUNTING CONNECTION TYPE SHOULD CORRELATE WITH THE
 ANCHOR CHARTS (SEE SHEET 11) FOR EXAMPLE, 1 (TOP) OR 5
 (BOTTOM).
  
 SUBSTRATE SHOULD BE THE SUBSTRATE FOR THE OPENING. THIS
 IS TYPICALLY CONCRETE ON THE TOP, BLOCK ON THE BOTTOM
 DUE TO EDGE DISTANCE REQUIREMENTS.
  
 ANCHOR SPACING - SELF EXPLANATORY. THIS COLUMN IS
 REQUIRED.
  
 2-3. OK
  
  