Plan Review Notes
Plan Review Notes For Permit 13080452
Permit Number 13080452
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-14 17:25:30ALARM SYSTEM IS BEING REQUIRED FOR THE PURPOSE OF
 MONITORING THE FLOW OF THE SPRINKLER SYSTEM. EACH UNIT
 IS EQUIPPED WITH SMOKE ALARMS PER THE REDIENTIAL CODE
 AND NO SOUNDER IS TO BE REQUIRED IN EACH UNIT BY THE
 EXCEPTIONS FOUND IN CHAPTER 9 UNDER R-2 SYSTEMS.
 PROTECTION OF LIFE IS PROVIDED BY THE SMOKE ALARMS AND
 PROTECTION OF PROPERTY IS TO BE AFFORDED BY THE
 SPRINKLER SYSTEM. DH 8/20/13
  
  
 PROVIDE OCCUPANT NOTIFICATION PER FBC 907.5
 [F] 907.5 OCCUPANT NOTIFICATION SYSTEMS.
 A FIRE ALARM SYSTEM SHALL ANNUNCIATE AT THE PANEL AND
 SHALL INITIATE OCCUPANT NOTIFICATION UPON ACTIVATION,
 IN ACCORDANCE WITH SECTIONS 907.5.1 THROUGH
 907.5.2.3.4. WHERE A FIRE ALARM SYSTEM IS REQUIRED BY
 ANOTHER SECTION OF THIS CODE, IT SHALL BE ACTIVATED BY:
  
 1. AUTOMATIC FIRE DETECTORS.
  
 2. SPRINKLER WATERFLOW DEVICES.
  
 3. MANUAL FIRE ALARM BOXES.
  
 4. AUTOMATIC FIRE-EXTINGUISHING SYSTEMS
  
 PROVIDE CLARIFICATION TO NOTE 17 OF THE FIRE ALARM
 NOTES.