2013-08-14 10:46:572010 FBC
  
 DENIED BY BUILDING
  
 1) THIS STRUCTURE IS LOCATED IN A 170 MPH VULT / 132
 MPH VASD WIND SPEED AND THE EXPOSURE CATEGORY IS D. THE
 REQUIRED UPLIFT FOR A ROOF SLOPE OF 0 TO 7 DEGREES WITH
 A 20 FT MEAN ROOF HEIGHT IS -82 PSF IN ROOF ZONE 2 AND
 -123 PSF IN ROOF ZONE 3. THE MAXIMUM DESIGN PRESSURE IS
 -60.0 PSF FOR THE SEALOFLEX W-5 SYSTEM THAT WAS
 SPECIFIED. THIS DESIGN PRESSURE DOES NOT MEET THE
 REQUIRED PRESSURES FOR ZONES 2 AND 3. ACCORDING TO THE
 PRODUCT APPROVAL NOTE #8 THE MAXIMUM DESIGN PRESSURE
 FOR FULLY BONDED ASSEMBLIES CAN NOT BE INCREASED BY
 RATIONAL ANALYSIS. PLEASE SUBMIT PRODUCT APPROVALS FOR
 A COMPLIANT ASSEMBLY. DCA RULE 9N-3
  