2013-08-12 11:14:392010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED 220 FEET FROM THE
 INTERCOASTAL WATERWAY, THEREFORE, IT IS CLASSIFIED AS
 EXPOSURE D. PLEASE REVISE RAS 117 CALCULATIONS FOR THE
 FLAT ROOF. FBC R301.2.1.4.3
  
 2) PROVIDE TWO COPIES OF A ROOF PLAN WITH THE
 DIMENSIONS FOR EACH AREA AND SPECIFY THE SLOPED & FLAT
 AREAS. SPECIFY THE PITCH OF THE SLOPED ROOF ON THE
 PLANS. FBC 107.2.1
  