2013-08-19 18:38:25RESIDENTIAL (R3) REVISION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PLANS SUBMITTED DON'T SHOW THE SIZE OF THE TRANSFER
 GRILLS ABOVE THE DOORS. THEREFORE, UNABLE TO VERIFY
 COMPLIANCE WITH SEC. M1602.4 EXCEPTION #2.
  
 2- BALANCED RETURN AIR IS FOR HABITABLE ROOMS ONLY.
 SEC. M1602.4 EXCEPTION #3. PLANS SHOW TRANSFER GRILLS
 ON THE BATHROOMS. REVISE AS REQUIRED.
  
  