Plan Review Notes For Permit 13080319 |
Permit Number |
13080319 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-08-19 18:38:25 | RESIDENTIAL (R3) REVISION, SECOND MECHANICAL REVIEW | | CHECKLIST. | | CODE: 2010 FBC. | | | | 1- PLANS SUBMITTED DON'T SHOW THE SIZE OF THE TRANSFER | | GRILLS ABOVE THE DOORS. THEREFORE, UNABLE TO VERIFY | | COMPLIANCE WITH SEC. M1602.4 EXCEPTION #2. | | | | 2- BALANCED RETURN AIR IS FOR HABITABLE ROOMS ONLY. | | SEC. M1602.4 EXCEPTION #3. PLANS SHOW TRANSFER GRILLS | | ON THE BATHROOMS. REVISE AS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|