Plan Review Notes
Plan Review Notes For Permit 13080300
Permit Number 13080300
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-12 15:52:28ONLY ONE SET OF PLANS PROVIDED. SCOPE OF WORK IS NOT
 CLEAR. DEFINE WHAT AND HOW MUCH IS BEING INSTALLED,
 REPLACED OR OTHERWISE. HOW MANY UNITS ARE ON THE
 PROPERTY? PROVIDE A RISER DIAGRAM, PANEL LOCATIONS,
 CIRCUIT DIRECTORY, LOAD CALCULATION, AVAILABLE FAULT
 CURRENT, AFCI, GFCI PROTECTION, PANEL DIRECTORY,
 EXTERIOR RECPTACLES, ROOM DESIGNATIONS, ETC. SO PLAN
 AND OTHER INFORMATION CAN BE EVALUATED. ADDITIONAL
 INFORMATION MAY BE REQUESTED UPON RESUBMISSION IF THAT
 INFORMATION IS FOUND TO CREATE ADDITIONAL QUESTIONS OR
 IS NOT IN COMPLIANCE WITH THE GOVERNING REGULATIONS. DH