Plan Review Notes For Permit 13080259 |
Permit Number |
13080259 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-09-12 10:00:49 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) ON SHEET A-101 THERE IS A NOTE FOR A NEW 3'-4" X | | 5'-0" IMPACT WINDOW POINTING TO THE DOUBLE OUT-SWING | | DOORS. PLEASE CLARIFY. INDICATE THE LOCATION OF THE NEW | | WINDOW ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | | 2) ON SHEET A-101 THERE IS A NOTE FOR A NEW 19'-0" X | | 8'-0" OVERHEAD GARAGE DOOR AT THE EXISTING GARAGE WHICH | | HAS A 9' WIDE OPENING. PLEASE CORRECT. CITY AMENDMENTS | | 107.2.1 | | | | 3) SHOW COMPLIANCE WITH FBCR 309.1 REQUIRES THE GARAGE | | FLOOR TO SLOPE TOWARD THE MAIN VEHICLE ENTRY DOORWAY. | | | | 4) ON SHEET A-103 WALL SECTIONS 3 & 4 SPECIFY 1/2" | | BOLTS TO ATTACH THE DOUBLE 2 X 8 LEDGER TO THE STUDS. | | PLEASE SPECIFY THE REQUIRED EMBED DEPTH OF THE LAGS | | INTO THE STUDS. FBCR 301.1 | | | | 5) PROVIDE A STRUCTURAL DETAIL FOR THE PARAPET WALLS | | INDICATING THE ATTACHMENTS AND CONNECTORS USED TO | | RESIST WIND-LOADS AND PROVIDE A CONTINUOUS LOAD PATH. | | FBCR 301.1 | | | | 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW | | OVERHEAD GARAGE DOORS, THE OUT-SWING DOUBLE DOORS, THE | | NEW WINDOW, THE TPO ROOFING MATERIAL, THE CLAY ROOF | | TILE, ROOFING ADHESIVES, AND SIMPSON CONNECTORS AS | | REQUIRED BY DCA RULE 9N-3. | | | | 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | AMENDMENTS 107.3.4.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|