2013-08-08 12:28:45RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ACCORDING TO PROPERTY APPRAISER THE HOUSE WAS
 DESIGNED WITH SHINGLES. RE-ROOF PERMIT APPLICATION
 SUBMITTED IS FOR CONCRETE TILE. NEED TO PROVIDE
 ENGINEERING CALCULATIONS SHOWING THAT THE EXISTING
 STRUCTURE IS CAPABLE OF SUPPORTING THE ADDITIONAL LOAD.
 SEC. 107.2.1.3 OF CITY AMENDMENTS TO FBC.
  
 2- ACCORDING TO THE LIMITATIONS OF BORAL ROOFING
 UNDERLAYMENT SUBMITTED THE FRSA/TRI 07320 DOESN'T
 ADDRESS WIND UPLIFT RESISTANCE OF DIRECT-DECK
 UNDERLAYMENTS SYSTEMS BENEATH A FOAM-ON TILE ATTACHMENT
 SYSTEM (SEE COPY OF LIMITATION #5.5.2 BELOW).
 THEREFORE, THE UPLIFT LIMITATION IS -45PSF (SEE COPY OF
 LIMITATION #5.5.2.1 BELOW). THIS LIMITATION DOESN'T
 MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 *****UNDERLAYMENT LIMITATIONS FROM FLORIDA PRODUCT
 APRPOVAL FL14317-R4 SUBMITTED:
  
 5.5.2
 FRSA/TRI 07320 DOES NOT ADDRESS WIND UPLIFT RESISTANCE
 OF DIRECT-DECK, ADHERED UNDERLAYMENT SYSTEMS BENEATH
 FOAM-ON TILE SYSTEMS, WHERE THE BONDED UNDERLAYMENT
 FORMS PART OF THE LOAD-PATH. THE FOLLOWING WIND UPLIFT
 LIMITATIONS APPLY TO DIRECT-DECK, ADHERED BORAL
 UNDERLAYMENT SYSTEMS.
 5.5.2.1
 MAXIMUM DESIGN PRESSURE = -45 PSF.
 DECK: MIN. 15/32-INCH PLYWOOD TO MEET PROJECT
 REQUIREMENTS TO SATISFACTION OF AHJ.
 PRIMER: (OPTIONAL) ASTM D41
 BASE LAYER: (OPTIONAL) CITADEL PLUS, SELF-ADHERED
 UNDERLAYMENT: BORAL TILESEALHT, SELF-ADHERED
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  
  