2013-08-08 10:07:00RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ACCORDING TO THE LIMITATIONS OF BORAL ROOFING
 UNDERLAYMENT SUBMITTED THE FRSA/TRI 07320 DOESN'T
 ADDRESS WIND UPLIFT RESISTANCE OF DIRECT-DECK
 UNDERLAYMENTS SYSTEMS BENEATH A FOAM-ON TILE ATTACHMENT
 SYSTEM (SEE COPY OF LIMITATION #5.5.2 BELOW).
 THEREFORE, THE UPLIFT LIMITATION IS -45PSF (SEE COPY OF
 LIMITATION #5.5.2.1 BELOW). THIS LIMITATION DOESN'T
 MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 *****UNDERLAYMENT LIMITATIONS FROM FLORIDA PRODUCT
 APRPOVAL FL14317-R4 SUBMITTED:
  
 5.5.2
 FRSA/TRI 07320 DOES NOT ADDRESS WIND UPLIFT RESISTANCE
 OF DIRECT-DECK, ADHERED UNDERLAYMENT SYSTEMS BENEATH
 FOAM-ON TILE SYSTEMS, WHERE THE BONDED UNDERLAYMENT
 FORMS PART OF THE LOAD-PATH. THE FOLLOWING WIND UPLIFT
 LIMITATIONS APPLY TO DIRECT-DECK, ADHERED BORAL
 UNDERLAYMENT SYSTEMS.
 5.5.2.1
 MAXIMUM DESIGN PRESSURE = -45 PSF.
 DECK: MIN. 15/32-INCH PLYWOOD TO MEET PROJECT
 REQUIREMENTS TO SATISFACTION OF AHJ.
 PRIMER: (OPTIONAL) ASTM D41
 BASE LAYER: (OPTIONAL) CITADEL PLUS, SELF-ADHERED
 UNDERLAYMENT: BORAL TILESEALHT, SELF-ADHERED
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712