Plan Review Notes
Plan Review Notes For Permit 13080214
Permit Number 13080214
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-08-09 11:50:561475 CENTERPARK BOULEVARD - SUITE #205
 PERMIT #13080214
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E2.1: NO EMERGENCY LIGHTING COULD BE LOCATED. PER
 NFPA 101 SECTION 39.2.9.1, EMERGENCY LIGHTING SHALL BE
 PROVIDED IN ANY BUILDING WHERE ANY ONE OF THE FOLLOWING
 CONDITIONS EXISTS:
 (1) THE BUILDING IS THREE OR MORE STORIES IN HEIGHT.
 (2) THE OCCUPANCY IS SUBJECT TO 100 OR MORE OCCUPANTS
 ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  